The Schneider Electric TeSys LX4D6KD is a replacement contactor coil for the LX1D6 contactor range, wound for 96 V DC control circuits. It carries a coil resistance of 51.9 Ohm at 68 °F (20 °C) and an inductance of 4.18 H when closed, which determines the inrush and hold current the control supply must deliver. Rated for a maximum operating rate of 3600 cycles per hour at 140 °F (60 °C), with mechanical durability rated at 10 million cycles. The ambient operating range spans 23 to 140 °F (-5 to 60 °C). This coil has no built-in suppressor module, so you must add an external flyback diode or RC snubber across the coil terminals when driven by a PLC or DC supply — the inductive kick at turn-off can damage solid-state outputs or create noise on the control bus.
The 96 V DC variant is less common than 24 V or 48 V coils, so verify the control voltage matches your panel's DC bus before committing the line item.