Schneider Electric LX4D7ZD — Contactor & Starter Coils

Schneider Electric LX4D7ZD TeSys Contactor Coil, 20 V DC, Ob

MPNLX4D7ZD
Obsolete

Schneider Electric TeSys Deca, contactor coil, LX4D7ZD, 20 V DC standard, for 80 A contactor, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX4D7ZD — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4D7
Coil technologyWithout built-in suppressor module
LX4D7ZD — Electrical
ParameterValue
Control circuit voltage [Uc]20 V DC
Control circuit typeDC standard
Control circuit voltage limitsDrop-out: 0.1...0.3 Uc (at Operational: 0.85...1.1 Uc (at <131 °F (55 °C))
Coil resistance (avg.)20.4 Ohm 68 °F (20 °C)
Time constant75 ms
LX4D7ZD — Power & Thermal
ParameterValue
Inrush power (W)22 W 68 °F (20 °C))
Hold-in power (W)22 W 68 °F (20 °C)
LX4D7ZD — Performance & Durability
ParameterValue
Max. operating rate3600 cyc/h 140 °F (60 °C)
Mechanical durability10 Mcycles
LX4D7ZD — Environmental
ParameterValue
Operating temperature23...140 °F (-5...60 °C)

Product details

It operates on a 20 V DC standard control circuit and is a service part for maintaining existing TeSys Deca installations.

Rated at 20 V DC control voltage, this coil is specific to DC control schemes — it will not work on an AC control transformer without a rectifier. The hold-in power consumption is 22 W at 68 °F (20 °C), with an inrush of the same value, meaning no separate pick-up/hold-in curve to manage. The coil has no built-in suppressor module, so you need to add a free-wheeling diode or varistor across the coil if the driving circuit requires transient suppression. That is a fast cycling rate — suitable for applications like conveyor indexing or rapid valve actuation, but the thermal limit at elevated ambient temperature should be respected. The control circuit voltage limits are: dropout at 0.1 to 0.3 Uc (2 to 6 V DC) and operational at 0.85 to 1.1 Uc (17 to 22 V DC) at below 131 °F (55 °C). This means the coil will reliably pick up at around 17 V DC and will drop out below about 6 V DC, giving a wide hysteresis that prevents chatter on a noisy DC bus.

Where this class of part is used

Contactor coils like this one are the replaceable actuation element in TeSys Deca contactors. They are used in motor control centers, panel boards, and industrial machinery where the contactor itself is a fixed installation and the coil is a serviceable wear item. The 20 V DC rating places it in DC control systems, common in battery-backed or PLC-driven panels.

Frequently asked questions

What is the closest pin-compatible alternative to LX4D7ZD?

No official direct replacement or pin-compatible alternative is specified in the manufacturer's records. For a drop-in replacement, you would need to cross-reference the coil's physical mounting, terminal arrangement, and 20 V DC rating against other TeSys Deca coils, or consider a contactor assembly swap.

What is the LX4D7ZD's listed range and category?

The LX4D7ZD belongs to the TeSys range, with the category listed as 18401-WORLD SERVICE PARTS (CTR ACCESS). It is a service part for contactor accessories.

How do I source the LX4D7ZD?

Since the part is obsolete, we can source it to order against an RFQ through our supply network. No stock or lead time can be guaranteed without a specific request; submit an RFQ for availability and pricing.

MPN
LX4D7ZD