Schneider Electric TeSys LX4FF027, contactor coil, 27 V DC, DC low consumption, without built-in suppressor module, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX4FF027 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FF
Coil technologyWithout built-in suppressor module
LX4FF027 — Electrical
ParameterValue
Control circuit voltage [Uc]27 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Coil resistance (avg.)1.44 Ohm inrush 68 °F (20 °C) 237.6 Ohm holding 68 °F (20 °C)
LX4FF027 — Performance & Durability
ParameterValue
Operating time30...40 ms closing 30...50 ms opening
LX4FF027 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The Schneider Electric LX4FF027 is a replacement contactor coil from the TeSys range, designed for DC low-consumption control circuits at 27 V DC nominal. It's a service part — the kind of item you order when a contactor in the field loses its coil and you need to swap the magnet assembly rather than replace the whole contactor block. The coil pulls in at 0.85 to 1.1 times Uc at 55 °C and drops out between 0.15 and 0.2 Uc — so on a 27 V DC bus it holds in down to roughly 23 V and releases somewhere around 4 to 5.4 V. Operating time runs 30 to 40 ms closing, 30 to 50 ms opening.

The 27 V DC coil voltage is the critical fit parameter — it must match the existing contactor's control voltage. The coil has no built-in suppressor module, so if your contactor base expects a suppressed coil or your DC bus has significant switching transients, you will need to add an external flyback diode or RC snubber across the coil terminals. Average resistance is 1.44 ohms inrush and 237.6 ohms holding at 20 °C, which gives you the steady-state current draw for your control transformer sizing.

Integration note

This is a coil-only replacement — it mounts onto the TeSys contactor magnet frame.

Frequently asked questions

What is the closest pin-compatible alternative?

No official successor or direct replacement order code is listed in the manufacturer's records for this part. For a drop-in fit, you would need to match the 27 V DC coil voltage, the TeSys contactor frame interface, and the mounting footprint. Contact us with your application details for cross-reference support.