Skip to main content
Schneider Electric LX4FF080 — Contactor & Starter Coils

Schneider Electric LX4FF080 TeSys contactor coil, 80 V DC

MPNLX4FF080
Active

Schneider Electric TeSys LX4FF080 contactor coil, 80 V DC, DC low consumption, without built-in suppressor module.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX4FF080 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FF
Coil technologyWithout built-in suppressor module
LX4FF080 — Electrical
ParameterValue
Control circuit voltage [Uc]80 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Coil resistance (avg.)10.67 Ohm inrush 68 °F (20 °C) 1823 Ohm holding 68 °F (20 °C)
LX4FF080 — Performance & Durability
ParameterValue
Operating time30...40 ms closing 30...50 ms opening
LX4FF080 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

Contactor coil for TeSys FF contactors

The LX4FF080 is a replacement contactor coil from the Schneider Electric TeSys range, designed for FF-frame contactors. It operates on an 80 V DC control circuit with low-consumption DC coil technology.

Operating characteristics and integration

Closing time is 30 to 40 ms; opening time is 30 to 50 ms. Control voltage limits are 0.85 to 1.1 Uc for operation at 55 °C, and dropout occurs between 0.15 and 0.2 Uc at 55 °C. This coil ships without a built-in suppressor module. For DC control circuits, you will need to add an external free-wheeling diode or varistor across the coil terminals to suppress the inductive kickback when de-energizing — otherwise the voltage spike can damage PLC output cards or relay contacts driving the coil.

Frequently asked questions

Does this coil include a built-in suppressor?

No, the coil technology is specified as without built-in suppressor module. An external free-wheeling diode or varistor must be added across the coil for DC applications to protect the control circuit from inductive voltage spikes.

What is the operating time of this coil?

Closing time is 30 to 40 ms; opening time is 30 to 50 ms.

What contactor frame does LX4FF080 fit?

It is designed for TeSys FF-frame contactors. The device short name is LX4FF, indicating the FF frame size.

MPN