Specifications

LX4FG060 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FG
Coil technologyWithout built-in suppressor module
LX4FG060 — Electrical
ParameterValue
Control circuit voltage [Uc]72 V DC
Control circuit typeDC wide range
Control circuit voltage limitsOperational 0.7...1.25 Uc 158 °F (70 °C)) Drop-out 0.2...0.45 Uc 158 °F (70 °C))
Coil resistance (avg.)5.07 Ohm inrush 68 °F (20 °C) 984 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)85 H
LX4FG060 — Power & Thermal
ParameterValue
Inrush power (W)800 W 68 °F (20 °C))
Hold-in power (W)5 W 68 °F (20 °C)
LX4FG060 — Performance & Durability
ParameterValue
Operating time30...40 ms closing 30...50 ms opening
Max. operating rate60 cyc/h 158 °F (70 °C)
Mechanical durability1 Mcycles
LX4FG060 — Environmental
ParameterValue
Operating temperature-67...158 °F (-55...70 °C)

Product details

Overview

The LX4FG060 is a Schneider TeSys F contactor coil, order code LX4FG060, rated for 72 V DC wide range control voltage and 800 W power handling, designed for use with TeSys F LC1F contactors. It draws 5 W of power consumption, has an inductance of 85 mH and a resistance of 5.07 Ω, and operates without a built-in suppressor module — the installer must add external suppression if the control circuit requires it.

This coil is the electromagnetic actuator that pulls in the main poles of a TeSys F contactor. The 72 V DC wide range control circuit accepts a broader voltage band than a standard DC coil, which helps maintain pickup on long cable runs where voltage drop is a concern. Because the coil ships without a built-in suppressor module, the panel builder must size and install an external flyback diode or RC snubber across the coil terminals to limit inductive kickback when the control circuit opens.

Applications

TeSys F contactor coils of this type are used in motor control centres, pump panels, conveyor drives and HVAC compressor starters where the contactor must be replaced or serviced independently of the power poles. The LX4FG060 specifically suits 72 V DC control systems common in industrial DC distribution or battery-backed control circuits.

MPN
LX4FG060