LX4FG140 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FG
Coil technologyWithout built-in suppressor module
LX4FG140 — Electrical
ParameterValue
Control circuit voltage [Uc]140 V DC
Control circuit typeDC wide range
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Coil resistance (avg.)24.3 Ohm inrush 68 °F (20 °C) 4958 Ohm holding 68 °F (20 °C)
LX4FG140 — Performance & Durability
ParameterValue
Operating time30...40 ms closing 30...50 ms opening
LX4FG140 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FG140 is a replacement contactor coil from the Schneider Electric TeSys range, part of the 18401-World Service Parts category. It is designed for DC wide-range control circuits and operates at a nominal 140 V DC, with an operational voltage window of 0.85...1.1 Uc at 131 °F (55 °C) and a drop-out threshold of 0.15...0.2 Uc. Coil resistance measures 24.3 Ohm inrush and 4958 Ohm holding at 68 °F (20 °C). The coil is supplied without a built-in suppressor module, so you will need to add external suppression if the application demands it — common on DC-switched inductive loads to protect the control contacts.

The 140 V DC control voltage is specific — not a common 24 V or 110 V DC coil. If your panel runs a 140 V DC control bus, this coil is a direct drop-in. The operating time of 30...40 ms closing and 30...50 ms opening is typical for a contactor coil of this size; it means the main contactor will pull in and drop out within that window, which matters for sequencing logic in a motor starter or transfer scheme.

Frequently asked questions

What is the closest alternative to the LX4FG140?

There is no official successor order code listed for the LX4FG140. The closest alternative would be a functionally equivalent contactor coil from the TeSys range with the same 140 V DC control voltage and mounting footprint, but you would need to verify pin compatibility and coil resistance against your specific contactor base.