Schneider Electric LX4FH080 — Contactor & Starter Coils

Schneider LX4FH080 TeSys contactor coil, 80 V DC

MPNLX4FH080
Active

Schneider Electric TeSys LX4FH080, contactor coil for FH series, 80 V DC control voltage, DC wide range, without built-in suppressor module.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX4FH080 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FH
Coil technologyWithout built-in suppressor module

Electrical

LX4FH080 — Electrical
ParameterValue
Control circuit voltage [Uc]80 V DC
Control circuit typeDC wide range
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Coil resistance (avg.)8.82 Ohm inrush 68 °F (20 °C) 1993 Ohm holding 68 °F (20 °C)

Performance & Durability

LX4FH080 — Performance & Durability
ParameterValue
Operating time40...50 ms closing 40...65 ms opening

Environmental

LX4FH080 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

What this coil is for

The Schneider Electric LX4FH080 is a replacement contactor coil in the TeSys range, designed for FH-series contactors. It is a DC wide-range coil rated at 80 V DC control voltage, meaning it operates within 0.85 to 1.1 Uc (68 to 88 V DC) and drops out between 0.15 and 0.2 Uc (12 to 16 V DC). The coil has no built-in suppressor module, so you will need to add external flyback diode or RC snubber protection across the coil terminals to protect the control circuit from inductive kickback.

Switching performance

Closing time is 40 to 50 ms; opening time is 40 to 65 ms. Average resistance is 8.82 ohms inrush and 1993 ohms holding at 20 °C. The coil is rated for ambient air temperatures from -5 to 55 °C. These figures matter for timing-dependent circuits like star-delta starters or reversing contactor interlocks where the opening delay window can affect mechanical overlap.

Frequently asked questions

What is the closest pin-compatible alternative to LX4FH080 in this component family?

There is no direct pin-compatible alternative at a different voltage within the FH series. The LX4FH080 is specific to 80 V DC control. If you need a different control voltage, you must select the corresponding LX4FH coil variant for that voltage — they share the same mechanical footprint but differ in winding resistance and voltage limits.

What is LX4FH080's listed range (TeSys) on this component line?

It belongs to the TeSys range, Schneider Electric's platform for contactors, overload relays, and control accessories.

What is LX4FH080's listed category (18401-WORLD SERVICE PARTS(CTR ACCESS)) on this component line?

The category 18401-WORLD SERVICE PARTS (CTR ACCESS) indicates this is a service part — a replacement coil for field-maintenance of FH contactors, not a full contactor assembly.

What compliance documentation does this brand provide for LX4FH080 (RoHS, REACH, UL, IEC)?

The evidence does not list specific compliance certifications for this order code. As a TeSys component, it typically carries CE marking and is designed to IEC/EN 60947 standards, but you should verify the specific declarations for your regulatory jurisdiction before ordering.