Schneider Electric LX4FH250 — Contactor & Starter Coils

TeSys LX4FH250 contactor coil, 250 V DC, obsolete

MPNLX4FH250
Obsolete

Schneider Electric TeSys F contactor coil, LX4FH250, 250 V DC control circuit, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX4FH250 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FH
Coil technologyWithout built-in suppressor module
LX4FH250 — Electrical
ParameterValue
Control circuit voltage [Uc]250 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 131 °F (55 °C))
Coil resistance (avg.)84 Ohm inrush 68 °F (20 °C) 13900 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)1910 H
LX4FH250 — Power & Thermal
ParameterValue
Inrush power (W)750 W 68 °F (20 °C))
Hold-in power (W)5 W 68 °F (20 °C)
LX4FH250 — Performance & Durability
ParameterValue
Operating time40...50 ms closing 40...65 ms opening
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX4FH250 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FH250 is a DC low-consumption contactor coil from the TeSys F range, designed to fit the corresponding TeSys F contactor frame. Rated for a 250 V DC control circuit, it pulls in at 750 W inrush and holds at 5 W, with an average inrush resistance of 84 Ohm and a holding resistance of 13900 Ohm at 68 °F (20 °C). Closing time runs 40 to 50 ms; opening time is 40 to 65 ms.

The 250 V DC coil is the key fit parameter — it is not a universal AC/DC coil. If your panel runs a 250 V DC control bus, this coil matches directly. The 0.85 to 1.1 Uc operational voltage range (212.5 to 275 V DC at 131 °F) gives some margin on a nominal 250 V bus, but the drop-out band of 0.15 to 0.2 Uc (37.5 to 50 V DC) means the contactor drops out cleanly on a low-voltage condition. The coil has no built-in suppressor module, so you will need an external flyback diode or RC snubber across the coil terminals to protect your DC control circuit from inductive kickback.

Mounts onto the TeSys F contactor base. The DC low-consumption design keeps thermal rise in the panel lower than an AC coil running through a rectifier — relevant if the contactor is in a sealed enclosure with limited airflow. Inductance of the closed circuit is 1910 H, which governs the inrush current profile and the sizing of any external suppression circuit.

Frequently asked questions

What is the control voltage for this coil?

250 V DC. The operational range is 0.85 to 1.1 Uc (212.5 to 275 V DC at 131 °F), with a drop-out range of 0.15 to 0.2 Uc (37.5 to 50 V DC at 131 °F).

Does this coil have a built-in suppressor?

No. It is specified as 'without built-in suppressor module'. An external flyback diode or RC snubber must be added across the coil terminals to suppress inductive voltage spikes.

What are the operating times for the LX4FH250?

Closing time is 40 to 50 ms; opening time is 40 to 65 ms.

What is the mechanical durability rating?

10 million cycles, with a maximum operating rate of 2400 cycles per hour at 131 °F (55 °C).

MPN
LX4FH250