Skip to main content
Schneider Electric LX4FJ030 — Contactor & Starter Coils

TeSys LX4FJ030 Contactor Coil, 30 V DC, Obsolete

MPNLX4FJ030
Obsolete

TeSys range, contactor coil, FJ frame, 30 V DC control voltage, DC low consumption, obsolete lifecycle stage.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX4FJ030 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FJ
Coil technologyWithout built-in suppressor module
LX4FJ030 — Electrical
ParameterValue
Control circuit voltage [Uc]30 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)0.842 Ohm inrush 68 °F (20 °C) 229.1 Ohm holding 68 °F (20 °C)
LX4FJ030 — Performance & Durability
ParameterValue
Operating time45...60 ms opening 50...60 ms closing
LX4FJ030 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FJ030 is a replacement contactor coil from the TeSys range, designed for FJ-frame contactors. It operates on a 30 V DC control circuit with DC low-consumption coil technology, meaning it draws inrush current only during pickup and then switches to a low holding current — a feature that reduces heat buildup in densely packed control panels.

Key electrical characteristics

The coil's operating time is 45 to 60 ms for opening and 50 to 60 ms for closing, which is typical for a contactor of this frame size and suitable for general motor switching and resistive load applications where fast but controlled engagement is needed. Average coil resistance measures 0.842 Ω during inrush and 229.1 Ω during holding at 68 °F (20 °C). The control circuit voltage limits are: dropout at 0.2 to 0.35 Uc (6 to 10.5 V DC) and operational range of 0.85 to 1.1 Uc (25.5 to 33 V DC) at 131 °F (55 °C). This means the coil will reliably pick up above ~25.5 V DC and drop out below ~10.5 V DC — important to verify your control supply stays within these bounds, especially on long cable runs where voltage drop is a factor. The coil comes without a built-in suppressor module, so an external flyback diode or RC snubber must be added across the coil terminals when driven by a PLC or solid-state output to prevent voltage spikes from damaging the driver.

Operating environment and category

Rated for ambient air temperatures from 23 to 131 °F (-5 to 55 °C) during operation, covering most indoor industrial control panel environments. The part is classified under category 18401-WORLD SERVICE PARTS (CTR ACCESS), indicating it is a service/replacement component rather than a new-design item.

Frequently asked questions

What is the closest alternative to the LX4FJ030?

No official successor order code is provided in the lifecycle record. The closest alternative would be a current-production TeSys FJ-frame contactor coil with 30 V DC control voltage, but mechanical fit (mounting pattern, plunger stroke) must be verified against your existing contactor before ordering.

What is the control voltage and coil technology of the LX4FJ030?

The LX4FJ030 uses a 30 V DC control circuit with DC low-consumption coil technology. It has no built-in suppressor module, so an external flyback diode is required when driven by electronic outputs.

What are the operating time and temperature range?

Opening time is 45 to 60 ms, closing time is 50 to 60 ms. Operating ambient temperature range is 23 to 131 °F (-5 to 55 °C).

MPN