Skip to main content
Schneider Electric LX4FJ036

Schneider Electric LX4FJ036 TeSys Contactor Coil, 36 V DC

MPN LX4FJ036
Active

Schneider Electric TeSys series, contactor coil LX4FJ036, 36 V DC control circuit, 45...60 ms opening time.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LX4FJ036 specifications
ParameterValue
Control circuit typeDC low consumption
Main product or component typeContactor coil
Coil voltage36 V DC
Temp operating max55 °C
Temp operating min-5 °C
Operating time45...60 ms opening 50...60 ms closing
Operating temperature23...131 °F (-5...55 °C)

Product details

Field-fit note for the LX4FJ036

This is the replacement coil for a TeSys FJ contactor frame, 36 V DC control. It pulls in at 0.85 to 1.1 Uc and drops out between 0.2 and 0.35 Uc at 55 °C — so if your control bus sags below about 7 V DC, the contactor drops. The coil draws about 1.3 Ω inrush, then holds at 347.6 Ω once sealed.

What the timing tells you

Opening time is 45 to 60 ms, closing 50 to 60 ms. That range is tight enough for most motor-start and lighting contactor circuits — no delayed dropout surprises on a fast-cycling load. No built-in suppressor module, so you'll want a free-wheeling diode or RC snubber across this coil if your PLC output card doesn't have one onboard.

Snaps onto the FJ contactor magnet assembly. Coil terminals are screw-clamp, same pitch as the contactor base. Strip 8 mm, torque to about 0.8 N·m. No polarity marking on the coil — it's DC but non-polarized, so you can swap the wires without issue.

MPN
LX4FJ036