Skip to main content
Schneider Electric LX4FJ075 — Contactor & Starter Coils

Schneider Electric LX4FJ075 TeSys Contactor Coil, 75 V DC

MPNLX4FJ075
Active

Schneider Electric TeSys F contactor coil, 75 V DC control voltage, DC low consumption, without built-in suppressor module.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX4FJ075 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FJ
Coil technologyWithout built-in suppressor module

Electrical

LX4FJ075 — Electrical
ParameterValue
Control circuit voltage [Uc]75 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)5.05 Ohm inrush 68 °F (20 °C) 1321 Ohm holding 68 °F (20 °C)

Performance & Durability

LX4FJ075 — Performance & Durability
ParameterValue
Operating time45...60 ms opening 50...60 ms closing

Environmental

LX4FJ075 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FJ075 is a TeSys F replacement coil for DC-operated contactors, rated at 75 V DC control voltage and built for low-consumption DC control circuits. It has no built-in suppressor module, so you'll need to add a free-wheeling diode or RC snubber across the coil if the driving PLC card or relay doesn't already handle flyback suppression. Opening time runs 45–60 ms, closing time 50–60 ms — typical for a contactor this size. The holding resistance at 68 °F (20 °C) is 1321 ohms, with an inrush resistance of 5.05 ohms at the same temperature. That inrush-to-hold ratio is what the DC low-consumption design optimises for: high pull-in force without cooking the coil during continuous duty.

The coil is rated for a control voltage of 75 V DC. Drop-out happens between 0.2 and 0.35 Uc (15 to 26 V DC) at 131 °F (55 °C); the operational range is 0.85 to 1.1 Uc (63.75 to 82.5 V DC) at the same temperature. If your DC supply sags below 64 V under load — say, during a simultaneous pickup of multiple contactors on a shared power supply — the coil may not pull in reliably. And if it drops below about 26 V, the contactor drops out, which could drop a motor or a heater load unexpectedly. Ambient operating temperature is rated from 23 to 131 °F (-5 to 55 °C).

Frequently asked questions

What is the closest alternative to the LX4FJ075 in the TeSys F family?

The TeSys F coil family includes several DC voltage ratings. The LX4FJ075 is the 75 V DC variant. Other voltages (24 V DC, 48 V DC, 110 V DC, etc.) use different order codes in the same LX4FJx form factor. If your control voltage differs, pick the coil that matches; the mechanical fit and contactor interface are the same across the family.

What compliance documentation is available for the LX4FJ075?

As a Schneider Electric TeSys component, the LX4FJ075 is manufactured to meet applicable IEC and UL standards for contactor accessories. Specific RoHS, REACH, and UL documentation is available from the manufacturer's product support pages or through your distributor's compliance team upon request.

MPN
LX4FJ075