Skip to main content
Schneider Electric LX4FJ200 — Contactor & Starter Coils

TeSys LX4FJ200 Contactor Coil, 200 V DC, Active

MPNLX4FJ200
Active

Schneider Electric TeSys FJ series contactor coil, LX4FJ200, 200 V DC control voltage, DC low-consumption type, active production.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX4FJ200 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FJ
Coil technologyWithout built-in suppressor module

Electrical

LX4FJ200 — Electrical
ParameterValue
Control circuit voltage [Uc]200 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)37.1 Ohm inrush 68 °F (20 °C) 9334 Ohm holding 68 °F (20 °C)

Performance & Durability

LX4FJ200 — Performance & Durability
ParameterValue
Operating time45...60 ms opening 50...60 ms closing

Environmental

LX4FJ200 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FJ200 is a 200 V DC contactor coil from the TeSys FJ series, designed as a replacement or build-up coil for TeSys FJ contactors. It's a DC low-consumption type, meaning the hold-in power draw is significantly lower than the inrush — the holding resistance at 20 °C is 9334 Ω versus 37.1 Ω for the inrush coil, so once the contactor seals, the coil driver sees a fraction of the initial current. The operating time is 45...60 ms opening and 50...60 ms closing, which is typical for a contactor of this frame size and keeps the switching sequence predictable for interlocking logic. The coil ships without a built-in suppressor module, so you'll need to add a flyback diode or RC snubber across the coil terminals if the DC control circuit drives it from a PLC output or relay — the inductive kick from a 200 V DC coil can damage solid-state outputs or cause noise issues on a shared 24 V DC backplane if left unsuppressed.

Control voltage and operating limits

Rated control circuit voltage is 200 V DC. The operational voltage limits are 0.85...1.1 Uc at 131 °F (55 °C), so the coil reliably picks up between 170 V DC and 220 V DC. Drop-out occurs at 0.2...0.35 Uc at 131 °F (55 °C), meaning the contactor drops out between 40 V DC and 70 V DC — wide enough to ride through minor sags but drops cleanly on a controlled shutdown. Ambient temperature range for operation is 23...131 °F (-5...55 °C), which covers most indoor control panel environments.

Frequently asked questions

What is LX4FJ200's listed range (TeSys) on this component line?

The LX4FJ200 belongs to the TeSys range, which is Schneider Electric's global line of contactors, motor starters, and control relays.

What is LX4FJ200's listed category (18401-WORLD SERVICE PARTS(CTR ACCESS)) on this component line?

The category is 18401-WORLD SERVICE PARTS(CTR ACCESS), indicating this is a service-part coil for contactors, not a main catalog product. It's stocked as a replacement component.

Does the LX4FJ200 include a built-in surge suppressor?

No, this coil is listed as 'Without built-in suppressor module'. You must add an external flyback diode or RC snubber when driving it from a DC control circuit.

MPN
LX4FJ200