Skip to main content
Schneider Electric LX4FK040 — Contactor & Starter Coils

Schneider Electric LX4FK040 TeSys Contactor Coil, 40 V DC

MPNLX4FK040
Active

Schneider Electric TeSys LX4FK040, contactor coil, 40 V DC, 45...60 ms opening, 50...60 ms closing.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX4FK040 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FK
Coil technologyWithout built-in suppressor module

Electrical

LX4FK040 — Electrical
ParameterValue
Control circuit voltage [Uc]40 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)1.56 Ohm inrush 68 °F (20 °C) 391.4 Ohm holding 68 °F (20 °C)

Performance & Durability

LX4FK040 — Performance & Durability
ParameterValue
Operating time45...60 ms opening 50...60 ms closing

Environmental

LX4FK040 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FK040 is a replacement contactor coil from the Schneider Electric TeSys range, designed for DC low-consumption control circuits at 40 V DC nominal. It opens in 45 to 60 ms and closes in 50 to 60 ms, with an average inrush resistance of 1.56 Ω and holding resistance of 391.4 Ω at 68 °F (20 °C). The coil has no built-in suppressor module, so you'll need to add external flyback suppression (a diode or RC snubber) across the coil terminals to protect the DC control circuit from inductive kickback.

Control voltage and operating limits

Rated control voltage is 40 V DC, with operational limits of 0.85 to 1.1 Uc (34 to 44 V DC) and dropout between 0.2 and 0.35 Uc (8 to 14 V DC), all at 131 °F (55 °C).

Frequently asked questions

What is the control voltage for LX4FK040?

The control circuit voltage is 40 V DC, with operational limits of 0.85 to 1.1 Uc (34 to 44 V DC) and dropout between 0.2 and 0.35 Uc (8 to 14 V DC) at 55 °C.

Does the LX4FK040 coil include a built-in suppressor?

No. The coil technology is listed as 'Without built-in suppressor module'. You must add external flyback suppression (diode or RC snubber) to protect the DC control circuit.

What is the operating temperature range for this coil?

Ambient air temperature for operation is 23 to 131 °F (-5 to 55 °C).

MPN