Skip to main content
Schneider Electric LX4FK200 — Contactor & Starter Coils

TeSys LX4FK200 Contactor Coil, 200 V DC, Obsolete

MPNLX4FK200
Obsolete

Schneider Electric TeSys range, contactor coil LX4FK200, 200 V DC control voltage, 45-60 ms opening, 50-60 ms closing.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX4FK200 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FK
Coil technologyWithout built-in suppressor module
LX4FK200 — Electrical
ParameterValue
Control circuit voltage [Uc]200 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)35.4 Ohm inrush 68 °F (20 °C) 8649 Ohm holding 68 °F (20 °C)
LX4FK200 — Performance & Durability
ParameterValue
Operating time45...60 ms opening 50...60 ms closing
LX4FK200 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FK200 is a contactor coil from the Schneider Electric TeSys range, designed to replace the coil in FK-series contactors. It operates on a 200 V DC control circuit with low-consumption DC coil technology. The coil pulls in with an inrush resistance of 35.4 Ω at 20 °C, then holds at 8649 Ω — the high holding resistance is what keeps power draw low once the contactor is sealed. Opening time is 45-60 ms, closing time 50-60 ms.

Control voltage limits and operating range

The coil is rated for 200 V DC nominal, with an operational range of 0.85 to 1.1 Uc at 55 °C. Drop-out occurs between 0.2 and 0.35 Uc at 55 °C. Ambient operating temperature is -5 to 55 °C. The coil ships without a built-in suppressor module — if your application needs flyback suppression, you add it externally.

No direct replacement is published. Verify coil voltage and mechanical fit against the existing contactor frame.

Frequently asked questions

What is the control voltage and operating time?

The coil is rated for 200 V DC control voltage. Opening time is 45-60 ms, closing time is 50-60 ms.

Does this coil include a built-in suppressor?

No. The LX4FK200 is listed as 'Without built-in suppressor module'. External flyback suppression must be added if required.

MPN
LX4FK200