MPNLX4FL200
Active

Schneider Electric TeSys LX4FL200, FK contactor coil, 200 V DC, without built-in suppressor module.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX4FL200 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FL
Coil technologyWithout built-in suppressor module

Electrical

LX4FL200 — Electrical
ParameterValue
Control circuit voltage [Uc]200 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))

Performance & Durability

LX4FL200 — Performance & Durability
ParameterValue
Operating time40...50 ms opening 60...70 ms closing

Environmental

LX4FL200 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX4FL200 is a TeSys FK contactor coil designed for 200 V DC control circuits. It is a service part (category 18401) for replacing or populating the coil on a compatible TeSys contactor frame. Opening time is 40 to 50 ms; closing time is 60 to 70 ms — a consistent, narrow band that matters when sequencing contactors in a motor starter or transfer scheme.

Control voltage and dropout behaviour

Rated control circuit voltage is 200 V DC. The coil drops out between 0.2 and 0.35 Uc at 131 °F (55 °C), and operates reliably from 0.85 to 1.1 Uc at the same temperature. That means the dropout threshold is well below the nominal hold level, giving a clean break without chatter. The coil has no built-in suppressor module. If the control circuit drives inductive loads or long wiring runs, an external flyback diode or RC snubber across the coil terminals is needed to protect the DC supply and limit EMI.

Frequently asked questions

What is the control voltage and what are the dropout/operational limits?

The coil is rated for 200 V DC control. Dropout occurs between 0.2 and 0.35 Uc (40 to 70 V DC) at 55 °C; operational range is 0.85 to 1.1 Uc (170 to 220 V DC) at 55 °C.

Does this coil include a built-in suppressor?

No — the coil is supplied without a built-in suppressor module. An external diode or RC snubber should be added if the control circuit requires transient suppression.

What are the opening and closing times?

Opening time is 40 to 50 ms; closing time is 60 to 70 ms.