Skip to main content
Schneider Electric LX4FL375 — Contactor & Starter Coils

TeSys LX4FL375 Contactor Coil, 375 V DC, Obsolete

MPNLX4FL375
Obsolete

TeSys F, contactor coil, LX4FL375, 375 V DC, DC low consumption, without built-in suppressor module.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX4FL375 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX4FL
Coil technologyWithout built-in suppressor module
LX4FL375 — Electrical
ParameterValue
Control circuit voltage [Uc]375 V DC
Control circuit typeDC low consumption
Control circuit voltage limitsDrop-out 0.2...0.35 Uc 131 °F (55 °C)) Operational 0.85...1.1 Uc 131 °F (55 °C))
Coil resistance (avg.)152 Ohm inrush 68 °F (20 °C) 23120 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)2910 H
LX4FL375 — Power & Thermal
ParameterValue
Inrush power (W)1600 W 68 °F (20 °C))
Hold-in power (W)9 W 68 °F (20 °C)
LX4FL375 — Performance & Durability
ParameterValue
Operating time40...50 ms opening 60...70 ms closing
Max. operating rate1200 cyc/h 131 °F (55 °C)
Mechanical durability5 Mcycles
LX4FL375 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

Coil Specifications and Fit

The LX4FL375: This is a 375 V DC control coil for the TeSys F contactor range. The control circuit is DC low consumption type, drawing 1600 W inrush and holding at 9 W at 20 °C. The coil has an average inrush resistance of 152 Ohm and a holding resistance of 23120 Ohm. The control circuit voltage limits are critical for reliable operation: drop-out occurs at 0.2 to 0.35 Uc (75 to 131 V DC) at 55 °C, and the operational range is 0.85 to 1.1 Uc (319 to 413 V DC) at 55 °C. Ensure your control supply stays within these bounds to avoid nuisance drop-out or coil damage. The coil is supplied without a built-in suppressor module. For DC switching, you must add an external flyback diode or varistor across the coil terminals to protect the control circuit from inductive kickback. The inductance of the closed circuit is 2910 H.

Operating Characteristics

Operating time is 40 to 50 ms for opening and 60 to 70 ms for closing. Maximum operating rate is 1200 cycles per hour at 55 °C. The ambient air temperature range for operation is -5 to 55 °C. This covers most indoor industrial panel environments but not extended cold storage or high-heat applications near furnaces.

Frequently asked questions

What is the closest alternative to LX4FL375 in the TeSys F family?

The LX4FL375 is a 375 V DC coil. The closest functional alternative would be another TeSys F coil with the same mechanical footprint and a DC control voltage that matches your supply. Check the control circuit voltage limits: drop-out at 0.2 to 0.35 Uc and operational at 0.85 to 1.1 Uc. A coil with a different voltage rating may not operate correctly in your circuit.

What compliance documentation is available for LX4FL375?

The manufacturer's lifecycle record does not include specific compliance documentation (RoHS, REACH, UL, IEC) for this obsolete part. For a replacement part, request the declaration of conformity from the manufacturer.

What is the operating time for LX4FL375?

Opening time is 40 to 50 ms; closing time is 60 to 70 ms. Maximum operating rate is 1200 cycles per hour at 55 °C.

MPN