Skip to main content
Schneider Electric LX9FF055 — Contactor & Starter Coils

TeSys LX9FF055 Contactor Coil, 55 V AC, Obsolete

MPNLX9FF055
Obsolete

Schneider Electric TeSys F series, LX9FF055 specific contactor coil, 55 V AC 40-400 Hz low consumption, 10 Mcycles mechanical durability.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FF055 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FF
Coil technologyWithout built-in suppressor module
LX9FF055 — Electrical
ParameterValue
Control circuit voltage [Uc]55 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 131 °F (55 °C))
Coil resistance (avg.)3.97 Ohm inrush 68 °F (20 °C) 100.2 Ohm holding 68 °F (20 °C)
LX9FF055 — Power & Thermal
ParameterValue
Inrush power (VA)690...855 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)6.6...8.1 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation5.9...7.2 W
LX9FF055 — Performance & Durability
ParameterValue
Operating time130 ms opening 35 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX9FF055 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FF055 is a specific replacement coil for TeSys F series contactors, wound for 55 V AC control circuits at 40-400 Hz. It's the low-consumption variant, meaning the hold-in power sits at 6.6-8.1 VA rather than the standard coil's draw — relevant if your control transformer is already loaded with PLCs and pilot lights. Opening time is 130 ms, closing 35 ms. Maximum operating rate is 2400 cycles per hour at 55 °C. Mechanical durability is 10 million cycles.

Coil Electrical Characteristics

The coil draws 690-855 VA inrush at 68 °F, dropping to 6.6-8.1 VA holding. Average resistance is 3.97 Ω inrush and 100.2 Ω holding at 20 °C. Control voltage limits: pick-up at 0.85-1.1 Uc, drop-out at 0.35-0.55 Uc at 55 °C. No built-in suppressor module.

Frequently asked questions

What is the closest alternative to LX9FF055?

There is no pin-compatible drop-in alternative. The current TeSys F coil range uses different voltage ratings and mounting. For a 55 V AC control circuit, you would need to replace the entire contactor assembly with a modern equivalent.

What is the LX9FF055's range and category?

It belongs to the TeSys range, category 22341-CONTACTOR,D,K,&F ACCESS. It is a specific contactor coil, not a complete contactor.

How do I source an obsolete LX9FF055?

Through the surplus and NOS channel. Submit an RFQ for a quote on available stock. No lead time can be guaranteed, but the part is findable through independent distributors.

MPN
LX9FF055