Skip to main content
Schneider Electric LX9FF080 — Contactor & Starter Coils

TeSys LX9FF080 Contactor Coil, 80 VAC, Obsolete

MPNLX9FF080
Obsolete

TeSys F specific contactor coil, 80 V AC 40..400 Hz low consumption, LX9FF080.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FF080 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FF
Coil technologyWithout built-in suppressor module
LX9FF080 — Electrical
ParameterValue
Control circuit voltage [Uc]80 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 131 °F (55 °C))
Coil resistance (avg.)7.54 Ohm inrush 68 °F (20 °C) 230.8 Ohm holding 68 °F (20 °C)
LX9FF080 — Power & Thermal
ParameterValue
Inrush power (VA)690...855 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)6.6...8.1 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation5.9...7.2 W
LX9FF080 — Performance & Durability
ParameterValue
Operating time130 ms opening 35 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX9FF080 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FF080 is a specific contactor coil from the TeSys F range, designed to operate at 80 V AC (40–400 Hz) with low-consumption control circuit technology. It is the replacement coil for TeSys F contactors that require a separate, field-replaceable coil — not a built-in or integrated coil assembly. The coil draws 690–855 VA inrush at 20 °C and settles to 6.6–8.1 VA holding power, with an average resistance of 7.54 Ω inrush and 230.8 Ω holding at 20 °C. Heat dissipation runs 5.9–7.2 W under steady-state operation. Opening time is 130 ms, closing time 35 ms.

Control voltage and operating limits

The coil operates across 0.85–1.1 Uc (68–88 V AC) at 55 °C and drops out between 0.35–0.55 Uc (28–44 V AC). This means the coil will hold in down to about 68 V and will reliably drop out below 44 V — important for brownout ride-through or undervoltage release coordination. Ambient temperature range for operation is -5 to 55 °C. The coil has no built-in suppressor module, so an external RC snubber or varistor must be added across the coil terminals if driving from a PLC output or solid-state relay to prevent inductive kickback damage.

This coil mounts onto TeSys F contactor bodies (LC1F range) as a field-replaceable component. The contactor itself is typically DIN-rail or panel-mounted in motor control centers, pump panels, and conveyor starters. The coil's AC control voltage means it is suited for installations where 80 V control transformers are already in place — common in older European-spec panels or retrofit scenarios.

Frequently asked questions

What is the closest alternative to LX9FF080?

No official successor order code is listed. Any replacement must be verified for pin-compatibility and electrical characteristics against the TeSys F contactor body it mates with. The coil footprint and mounting interface are specific to the LC1F contactor range.

What is the control voltage and frequency range?

The LX9FF080 is rated for 80 V AC control voltage, 40–400 Hz. It operates between 68–88 V AC (0.85–1.1 Uc) and drops out between 28–44 V AC (0.35–0.55 Uc) at 55 °C.

Does the coil include a built-in suppressor?

No, the coil technology is listed as 'without built-in suppressor module'. An external RC snubber or varistor must be added across the coil terminals when driven by a PLC output or solid-state relay.

MPN
LX9FF080