Skip to main content
Schneider Electric LX9FG550 — Contactor & Starter Coils

Schneider LX9FG550 TeSys F contactor coil, 550 V AC, obsolet

MPNLX9FG550
Obsolete

Schneider Electric TeSys F specific contactor coil, LX9FG550, 550 V AC 40...400 Hz low consumption, 130 ms opening / 35 ms closing, obsolete lifecycle.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FG550 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FG
Coil technologyWithout built-in suppressor module
LX9FG550 — Electrical
ParameterValue
Control circuit voltage [Uc]550 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.2...0.55 Uc 131 °F (55 °C))
Coil resistance (avg.)194 Ohm inrush 68 °F (20 °C) 7550 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)26.3 H
LX9FG550 — Power & Thermal
ParameterValue
Inrush power (VA)950...1180 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)8.9...10.9 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation8...9.8 W
LX9FG550 — Performance & Durability
ParameterValue
Operating time130 ms opening 35 ms closing
Max. operating rate2400 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles
LX9FG550 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FG550 is a specific replacement coil for the TeSys F contactor range, designed for a 550 V AC control circuit at 40...400 Hz with low-hold-in consumption. It draws 950...1180 VA inrush and settles to 8.9...10.9 VA holding, with an average resistance of 194 Ω inrush and 7550 Ω holding at 68 °F (20 °C). The coil operates without a built-in suppressor module, so the panel builder must add external suppression (RC snubber or varistor) across the coil terminals if driving from a PLC output or electronic controller — the inductive kick from the 26.3 H closed-circuit inductance will otherwise stress solid-state drivers.

Rated control voltage is 550 V AC. The operational voltage window is 0.85...1.1 Uc at 131 °F (55 °C), and drop-out occurs between 0.2...0.55 Uc. Operating time is 130 ms opening and 35 ms closing. The 35 ms close is fast for a 550 V coil; the 130 ms open is comparatively slow — factor this into safety circuit response time calculations if the coil is part of a guard-monitoring chain.

Deployment context

This coil mounts onto a TeSys F contactor in a control panel — typically DIN-rail or backplate mounted. The 550 V AC control circuit is common in 480 V line-voltage motor starters where the control transformer is omitted and the coil is fed directly from the line side through a control fuse. The ambient temperature range of -5...55 °C covers most indoor industrial environments, but the coil's heat dissipation of 8...9.8 W means it contributes to the panel's thermal load. In a densely packed enclosure with multiple TeSys F contactors running continuously, forced ventilation or a larger enclosure may be needed to stay within the rated ambient.

Frequently asked questions

What is the closest alternative to the LX9FG550?

No official successor order code is listed in the lifecycle record. The buyer should verify the contactor frame size and coil mounting interface; a substitute from the same TeSys F range with the same 550 V AC rating and low-consumption specification may be functionally equivalent, but pin compatibility must be confirmed against the contactor's coil terminal layout.

Does this coil include a built-in suppressor?

No. The coil technology is listed as without built-in suppressor module. External suppression (RC snubber or varistor) must be added when driving from electronic outputs.

What is the operating time of this coil?

130 ms opening and 35 ms closing. The 35 ms close is fast; the 130 ms open is relatively slow and should be considered in safety circuit timing.

MPN