Schneider Electric LX9FH1902 — Contactor & Starter Coils

Schneider Electric LX9FH1902 TeSys F Contactor Coil, 190 V A

MPNLX9FH1902
Obsolete

Schneider Electric TeSys F specific contactor coil, LX9FH1902, 190 V AC 40-400 Hz low consumption, inrush 560-660 VA, hold-in 8-10 VA.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX9FH1902 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FH
Coil technologyWithout built-in suppressor module

Electrical

LX9FH1902 — Electrical
ParameterValue
Control circuit voltage [Uc]190 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 131 °F (55 °C))
Coil resistance (avg.)45.6 Ohm inrush 68 °F (20 °C) 1054 Ohm holding 68 °F (20 °C)

Power & Thermal

LX9FH1902 — Power & Thermal
ParameterValue
Inrush power (VA)560...660 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)8...10 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation8.4...10.4 W

Performance & Durability

LX9FH1902 — Performance & Durability
ParameterValue
Operating time25 ms opening 45 ms closing
Max. operating rate3600 cyc/h 131 °F (55 °C)
Mechanical durability10 Mcycles

Environmental

LX9FH1902 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FH1902 is a specific contactor coil from the Schneider Electric TeSys F range, designed as the replaceable coil assembly for TeSys F contactors. It operates on a 190 V AC control circuit at 40-400 Hz and is classed as low-consumption type, drawing 560-660 VA inrush and only 8-10 VA holding power at 68 °F (20 °C).

The 190 V AC control voltage (40-400 Hz) is the coil's nominal pick-up voltage — not a universal 120 V or 240 V coil. The operational limits are 0.85-1.1 Uc at 131 °F (55 °C), meaning it reliably picks up between about 162 V and 209 V AC. Drop-out occurs between 0.35-0.55 Uc (roughly 67-105 V AC), so a brownout below that threshold will release the contactor. Inrush power of 560-660 VA at 40-400 Hz determines the peak load the control transformer or PLC output must handle during pick-up. The steady-state hold-in drops to 8-10 VA, which is what the coil draws continuously once the contactor is sealed. Coil resistance measures 45.6 Ω inrush and 1054 Ω holding at 68 °F (20 °C). Opening time is 25 ms, closing time 45 ms — these are the mechanical response times of the contactor assembly with this coil fitted. Maximum operating rate is 3600 cycles per hour at 131 °F (55 °C), which governs how fast the contactor can cycle in high-duty applications like conveyor indexing or press control. Heat dissipation runs 8.4-10.4 W, which must be accounted for in enclosure thermal calculations, especially when multiple contactors are ganged in a panel.

Coil technology note

This coil is supplied without a built-in suppressor module. For applications where transient suppression is required — such as when the coil is driven by a PLC output or solid-state relay — an external RC snubber or varistor must be added across the coil terminals to protect the switching device from inductive kickback.

Operating environment

Rated for ambient air temperatures of -5 °C to 55 °C (23-131 °F). This covers most indoor industrial panel environments but does not extend to extreme cold storage or high-heat zones near furnaces without derating.

Frequently asked questions

What is the LX9FH1902's control voltage and frequency range?

The coil is rated for 190 V AC at 40-400 Hz. It picks up reliably between 0.85-1.1 Uc (approximately 162-209 V AC) and drops out between 0.35-0.55 Uc (approximately 67-105 V AC) at 55 °C.

Does the LX9FH1902 include a built-in surge suppressor?

No. This coil is supplied without a built-in suppressor module. An external RC snubber or varistor must be added if the coil is driven by a PLC output or solid-state relay to suppress inductive kickback.

What is the inrush and holding power consumption of this coil?

Inrush power is 560-660 VA at 40-400 Hz. Holding power drops to 8-10 VA once the contactor is sealed. Coil resistance is 45.6 Ω inrush and 1054 Ω holding at 68 °F (20 °C).

What is the mechanical durability and maximum operating rate?

Mechanical durability is rated at 10 million cycles. Maximum operating rate is 3600 cycles per hour at 55 °C (131 °F). Opening time is 25 ms, closing time 45 ms.