Schneider LX9FJ916 TeSys F Contactor Coil, 42 V AC/DC, 500 V

MPNLX9FJ916
Active

Schneider Electric TeSys F, specific contactor coil, LX9FJ916, 42 V AC 40-400 Hz / 42 V DC, 500 VA inrush, 11.4-13.9 W heat dissipation.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX9FJ916 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FJ
Coil technologyWithout built-in suppressor module

Electrical

LX9FJ916 — Electrical
ParameterValue
Control circuit voltage [Uc]42 V AC 40...400 Hz 42 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
Coil resistance (avg.)4.03 Ohm inrush 68 °F (20 °C) 43 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)0.22 H

Power & Thermal

LX9FJ916 — Power & Thermal
ParameterValue
Inrush power (VA)500 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)23 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation11.4...13.9 W

Performance & Durability

LX9FJ916 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles

Environmental

LX9FJ916 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

Coil for TeSys F contactors — 42 V AC/DC, no built-in suppressor

The LX9FJ916 is a specific replacement coil for the TeSys F contactor range, wound for 42 V AC (40–400 Hz) or 42 V DC control. It draws 500 VA inrush at 20 °C, settling to 23 VA holding, with a closed-circuit inductance of 0.22 H. The coil has no built-in suppressor module — you supply the external flyback diode (DC) or RC snubber (AC) across the terminals; omitting it will arc the control contacts on dropout. Operating times are 60 ms opening, 20 ms closing. That 3:1 open-to-close ratio matters in safety circuits where the contactor must drop out faster than it picks — verify your PLC cycle time can tolerate the 60 ms break before re-energizing.

Electrical and thermal limits

Coil resistance measures 4.03 Ω inrush and 43 Ω holding at 20 °C. Heat dissipation runs 11.4 to 13.9 W — enough to raise the temperature inside a crowded enclosure; keep adjacent wiring and smaller components clear of the coil body. The control voltage limits are 0.85–1.1 Uc for pickup (at 55 °C) and 0.3–0.5 Uc for dropout, so a 42 V nominal coil picks reliably at 35.7 V and drops between 12.6 and 21 V. Rated for 10 Mcycles mechanical endurance and a maximum operating rate of 3600 cycles per hour at 70 °C. That rate is the coil's thermal limit, not the contactor's — if the contactor carries heavy motor loads, the switching frequency will be lower.

Frequently asked questions

What is the control voltage for this coil?

42 V AC (40–400 Hz) or 42 V DC. Pickup range is 0.85–1.1 Uc at 55 °C; dropout is 0.3–0.5 Uc.

Does this coil include a built-in suppressor?

No. The coil has no built-in suppressor module. An external flyback diode (DC) or RC snubber (AC) must be added across the coil terminals to protect the control circuit from inductive kickback.

What is the heat dissipation of this coil?

11.4 to 13.9 W, depending on the control voltage and temperature. Account for this thermal load in your enclosure sizing.