Skip to main content
Schneider Electric LX9FJ917 — Contactor & Starter Coils

Schneider LX9FJ917 TeSys F Contactor Coil, 48 V AC/DC, Obsol

MPNLX9FJ917
Obsolete

Schneider Electric TeSys F, specific contactor coil, LX9FJ917, 48 V AC 40...400 Hz low consumption, 48 V DC low consumption, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FJ917 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FJ
Coil technologyWithout built-in suppressor module
LX9FJ917 — Electrical
ParameterValue
Control circuit voltage [Uc]48 V AC 40...400 Hz 48 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
Coil resistance (avg.)4.03 Ohm inrush 68 °F (20 °C) 43 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)0.22 H
LX9FJ917 — Power & Thermal
ParameterValue
Inrush power (VA)500 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)23 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation11.4...13.9 W
LX9FJ917 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles
LX9FJ917 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FJ917 is a specific replacement coil for the TeSys F contactor range, designed for 48 V AC (40–400 Hz) or 48 V DC control circuits. It's a low-consumption coil — 23 VA holding at 68 °F, 500 VA inrush — which means the control transformer sizing is tighter than a standard coil; the inrush spike is brief but real. Opening time is 60 ms, closing 20 ms, so the contactor responds fast enough for most motor-start and isolation duties.

Key electrical specs at a glance

Control voltage is 48 V AC (40–400 Hz) or 48 V DC. The coil draws 500 VA inrush and 23 VA holding on AC; DC holding is lower. Average resistance is 4.03 Ω inrush and 43 Ω holding at 68 °F (20 °C). Heat dissipation runs 11.4 to 13.9 W, so panel thermal rise is a consideration if multiple coils are ganged. The coil has no built-in suppressor module — you'll need an external RC snubber or free-wheeling diode across the coil if driving from a PLC output or solid-state relay, otherwise the inductive kick can damage the driver.

Frequently asked questions

What is the operating temperature range for this coil?

Ambient air temperature for operation is 23 to 131 °F (-5 to 55 °C).

Does this coil include a built-in suppressor module?

No. The coil technology is listed as 'without built-in suppressor module'. An external suppression device (RC snubber or diode) is required when switching with electronic outputs.

MPN
LX9FJ917