Skip to main content
Schneider Electric LX9FJ929 — Contactor & Starter Coils

LX9FJ929 TeSys F contactor coil, 157-175 V DC / 180 V AC

MPNLX9FJ929
Active

Schneider Electric TeSys F series, LX9FJ929 specific contactor coil, 157-175 V DC / 180 V AC 40-400 Hz, 500 VA inrush, 60 ms opening / 20 ms closing, without built-in suppressor module.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX9FJ929 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FJ
Coil technologyWithout built-in suppressor module

Electrical

LX9FJ929 — Electrical
ParameterValue
Control circuit voltage [Uc]157...175 V DC 180 V AC 40...400 Hz
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))

Power & Thermal

LX9FJ929 — Power & Thermal
ParameterValue
Inrush power (VA)500 VA 40...400 Hz (at 68 °F (20 °C))
Hold-in power (VA)23 VA 40...400 Hz (at 68 °F (20 °C))
Heat dissipation11.4...13.9 W

Performance & Durability

LX9FJ929 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles

Environmental

LX9FJ929 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

Coil for TeSys F contactors — what fits and what doesn't

The LX9FJ929 is a specific replacement coil for the TeSys F contactor range. It's the part you swap when the coil burns open or the control voltage changes on an existing contactor — not a standalone contactor itself. Rated for 157-175 V DC or 180 V AC 40-400 Hz, so it handles both a DC control bus and an AC control transformer on the same coil, but not simultaneously. Opening time is 60 ms, closing time 20 ms. That matters when you're sequencing contactors in a star-delta start or reversing drum: the slower open gives the arc time to clear, the fast close keeps arcing duration short on make. No built-in suppressor module. That means you need an external flyback diode for DC control or an RC snubber for AC if the PLC output or relay driving it doesn't have one onboard. The coil draws 500 VA inrush at 20°C, dropping to 23 VA hold-in — size the control transformer for the inrush, not the sealed VA.

Electrical and thermal limits for panel integration

Heat dissipation runs 11.4 to 13.9 W when sealed. That's not trivial in a crowded enclosure — account for it in the thermal budget, especially if the contactor is mounted next to other heat sources like power supplies or drives. That suits high-cycle applications like conveyor sortation or packaging lines where the contactor cycles every second. Drop-out voltage is 0.3 to 0.5 Uc at 55°C — the coil drops out cleanly between 47 and 87 V DC, so it won't chatter on a sagging bus.

What the category code tells you

The category 22341 maps to contactor accessories — specifically coils for the TeSys D, K, and F ranges. This LX9FJ929 is the F-range variant, physically larger than the D/K coils and with higher inrush. Don't cross-fit a D-range coil into an F contactor; the mounting flange and magnetic circuit are different.

Frequently asked questions

What control voltages does this coil accept?

Dual-rated for 157-175 V DC and 180 V AC 40-400 Hz. The operational limits are 0.85 to 1.1 Uc at 55°C, so it holds in down to about 133 V DC or 153 V AC. Drop-out range is 0.3 to 0.5 Uc.

Does this coil include a built-in surge suppressor?

No. The coil technology is listed as 'without built-in suppressor module'. You must add an external flyback diode for DC control or an RC snubber for AC to protect the driving contact or PLC output from the inductive kick.

What is the inrush and hold-in power consumption?

Inrush is 500 VA at 20°C, dropping to 23 VA hold-in. Size the control transformer for the inrush peak, not the sealed VA. Heat dissipation once sealed is 11.4 to 13.9 W.

What operating temperature range and cycle rate does it support?

Operating ambient is -5 to 55°C. Maximum operating rate is 3600 cycles per hour at 70°C. Mechanical life is 10 million cycles.

MPN