Skip to main content
Schneider Electric LX9FK933 — Contactor & Starter Coils

Schneider Electric LX9FK933 TeSys F Contactor Coil, 250-283

MPNLX9FK933
Obsolete

Schneider Electric TeSys F specific contactor coil, LX9FK933, 250-283 V DC low consumption, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FK933 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FK
Coil technologyWithout built-in suppressor module
LX9FK933 — Electrical
ParameterValue
Control circuit voltage [Uc]250...283 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
LX9FK933 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA (at 68 °F (20 °C))
Hold-in power (VA)31 VA (at 68 °F (20 °C))
Heat dissipation15...18.3 W
LX9FK933 — Performance & Durability
ParameterValue
Operating time60 ms opening 50 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles
LX9FK933 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FK933 is a specific contactor coil from the Schneider Electric TeSys F range, designed to actuate TeSys F contactors. It operates on a 250-283 V DC control circuit and is classified as low consumption, drawing 550 VA inrush and 31 VA hold-in power at 20 °C. The coil has a mechanical durability of 10 million cycles and a maximum operating rate of 3600 cycles per hour at 70 °C. Opening time is 60 ms, closing time is 50 ms.

The coil dissipates 15-18.3 W of heat, which should be factored into panel thermal calculations if a replacement or equivalent is being sourced. The control circuit accepts AC 40-400 Hz or DC low-consumption drive, but this specific variant is DC-only at 250-283 V.

Integration notes

The coil comes without a built-in suppressor module, so an external RC snubber or free-wheeling diode must be added across the coil terminals if driving from a PLC output or solid-state relay — otherwise the inductive kickback can damage the control circuit. Operational voltage limits are 0.85-1.1 Uc at 55 °C, with dropout at 0.3-0.5 Uc. These define the real-world hold-in and dropout margins for a panel environment.

Frequently asked questions

What is the control circuit voltage for this coil?

The control circuit voltage is 250-283 V DC, with operational limits of 0.85-1.1 Uc at 55 °C and dropout at 0.3-0.5 Uc.

What is the operating time of the LX9FK933?

Opening time is 60 ms and closing time is 50 ms.

Does the LX9FK933 include a built-in suppressor module?

No, the coil technology is listed as without built-in suppressor module. An external suppression network is required for inductive load switching.