Skip to main content
Schneider Electric LX9FK935 — Contactor & Starter Coils

TeSys LX9FK935 specific contactor coil, 321-352 V DC, obsole

MPNLX9FK935
Active

Schneider Electric TeSys F specific contactor coil, LX9FK935, 321-352 V DC low consumption, 550 VA inrush, 31 VA hold-in, 10 Mcycles mechanical durability.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FK935 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FK
Coil technologyWithout built-in suppressor module
LX9FK935 — Electrical
ParameterValue
Control circuit voltage [Uc]321...352 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
LX9FK935 — Power & Thermal
ParameterValue
Inrush power (VA)550 VA (at 68 °F (20 °C))
Hold-in power (VA)31 VA (at 68 °F (20 °C))
Heat dissipation15...18.3 W
LX9FK935 — Performance & Durability
ParameterValue
Operating time60 ms opening 50 ms closing
Max. operating rate3600 cyc/h 158 °F (70 °C)
Mechanical durability10 Mcycles
LX9FK935 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FK935 is a specific contactor coil from the Schneider Electric TeSys F range, designed to operate a TeSys F contactor when energized with 321-352 V DC. It is a low-consumption coil — draws 550 VA inrush at 20 °C, then settles to 31 VA hold-in power — so the control transformer and wiring can be sized for the peak, not the steady-state. Opening time is 60 ms, closing 50 ms, which is typical for a DC-operated coil of this frame size. The coil has no built-in suppressor module, so an external flyback diode or RC snubber must be added across the coil terminals when driven by a PLC or solid-state output — otherwise the inductive kick can damage the driver.

The control circuit voltage is 321-352 V DC. Operational limits are 0.85 to 1.1 Uc at 55 °C; drop-out occurs between 0.3 and 0.5 Uc. The maximum operating rate is 3600 cycles per hour at 70 °C — that is one cycle per second, which is fast for a DC coil; verify the contactor's own mechanical limit if cycling at that rate.

Frequently asked questions

What is the closest alternative to LX9FK935?

There is no official direct replacement from Schneider Electric for this specific coil voltage and frame. The TeSys F range is superseded by newer families, but a drop-in form-fit-function equivalent does not exist. You would need to replace the entire contactor assembly with a current-series unit, or source the LX9FK935 through surplus.

Does this coil include a built-in suppressor?

No, it is supplied without a built-in suppressor module. An external flyback diode or RC snubber must be added when driven by electronic outputs.

MPN
LX9FK935