Skip to main content
Schneider Electric LX9FL911 — Contactor & Starter Coils

TeSys LX9FL911 Specific Contactor Coil, 22-23 V DC Low Consu

MPNLX9FL911
Active

Schneider Electric TeSys F, specific contactor coil, LX9FL911, 22...23 V DC low consumption, 48 W hold-in, 5 Mcycles mechanical durability.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FL911 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FL
Coil technologyWithout built-in suppressor module
LX9FL911 — Electrical
ParameterValue
Control circuit voltage [Uc]22...23 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
LX9FL911 — Power & Thermal
ParameterValue
Inrush power (W)733 W 68 °F (20 °C))
Hold-in power (W)48 W 68 °F (20 °C)
Heat dissipation22.8...27.8 W
LX9FL911 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate1800 cyc/h 158 °F (70 °C)
Mechanical durability5 Mcycles
LX9FL911 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FL911: The coil draws 48 W hold-in power at 68 °F (20 °C) and dissipates 22.8...27.8 W in continuous service. Operating time is 60 ms opening and 20 ms closing.

It ships as a single unit per package, so if you're stocking spares for a line with multiple TeSys F contactors, order the quantity you need — no bulk minimums implied. The coil uses AC 40...400 Hz or DC low-consumption control circuit technology, with no built-in suppressor module. That means you'll need to add an external flyback diode or RC snubber across the coil if your PLC output or relay driving it doesn't have one built in.

Mechanical and thermal limits

Rated for 5 Mcycles mechanical durability. Maximum operating rate is 1800 cycles per hour at 158 °F (70 °C). Ambient operating temperature range is 23...131 °F (-5...55 °C). The inrush power is 733 W at 68 °F (20 °C) — that's the initial pull-in surge, which drops to the 48 W hold-in once the contactor seals. Make sure your control transformer or DC supply can handle that momentary surge without voltage sag.

Frequently asked questions

Does this coil include a built-in suppressor module?

No, the LX9FL911 is specified as 'without built-in suppressor module'. You'll need to add an external flyback diode or RC snubber across the coil terminals to protect the driving circuit from inductive kickback when the coil de-energizes.

What is the heat dissipation of this coil?

The LX9FL911 dissipates 22.8...27.8 W in continuous operation. That's the heat load it adds to the contactor body and the enclosure — account for it in your panel thermal calculations, especially in sealed cabinets with multiple contactors.

MPN