TeSys F, specific contactor coil, LX9FL920, 59..65 V DC low consumption, 60 ms opening / 20 ms closing, heat dissipation 22.8...27.8 W.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LX9FL920 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FL
Coil technologyWithout built-in suppressor module

Electrical

LX9FL920 — Electrical
ParameterValue
Control circuit voltage [Uc]59...65 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))

Power & Thermal

LX9FL920 — Power & Thermal
ParameterValue
Inrush power (W)733 W 68 °F (20 °C))
Hold-in power (W)48 W 68 °F (20 °C)
Heat dissipation22.8...27.8 W

Performance & Durability

LX9FL920 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate1800 cyc/h 158 °F (70 °C)
Mechanical durability5 Mcycles

Environmental

LX9FL920 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FL920 is a specific contactor coil from the TeSys F range, designed as a replacement or spare coil for TeSys F contactors. It operates on a control circuit voltage of 59...65 V DC and is classed as low consumption — meaning it draws less steady-state power than a standard AC or DC coil of the same frame size. Opening time is 60 ms, closing time is 20 ms. The coil has no built-in suppressor module, so you'll need to add an external RC snubber or flyback diode across the coil terminals if driving it from a PLC output or solid-state relay. Heat dissipation runs 22.8...27.8 W, which matters for panel thermal budgeting — especially if multiple contactors are ganged in a small enclosure. Inrush power at 20 °C is 733 W, but that's a transient; the hold-in power settles to 48 W at the same temperature.

Because it's a specific coil (not a universal replacement), confirm the mating contactor frame and the control voltage range before committing the line.

Installation and integration notes

The coil accepts AC control supply from 40 to 400 Hz as well as DC, but the rated voltage range is 59...65 V DC. Operational limits are 0.85...1.1 Uc at 55 °C; dropout occurs between 0.3...0.5 Uc at the same temperature. Ambient operating temperature is -5...55 °C. That's adequate for most motor-starting and resistive-load switching applications in a standard industrial panel.

Frequently asked questions

What is the control voltage for the LX9FL920?

The control circuit voltage is 59...65 V DC. It also accepts AC supply from 40 to 400 Hz, but the rated DC range is the one to design around.

Does the LX9FL920 include a built-in suppressor module?

No, the coil technology is listed as 'Without built-in suppressor module'. An external snubber or flyback diode must be added for inductive-load switching.

What is the operating temperature range for this coil?

Ambient air temperature for operation is -5 to 55 °C. The maximum operating rate of 1800 cycles per hour is specified at 70 °C.