Skip to main content
Schneider Electric LX9FL926 — Contactor & Starter Coils

TeSys LX9FL926 specific contactor coil, 127 V DC, obsolete

MPNLX9FL926
Obsolete

TeSys F, specific contactor coil, 127 V DC low consumption, LX9FL926.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FL926 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FL
Coil technologyWithout built-in suppressor module
LX9FL926 — Electrical
ParameterValue
Control circuit voltage [Uc]127 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
Coil resistance (avg.)20.8 Ohm inrush 68 °F (20 °C) 167 Ohm holding 68 °F (20 °C)
Coil inductance (closed circuit)1.2 H
LX9FL926 — Power & Thermal
ParameterValue
Inrush power (W)733 W 68 °F (20 °C))
Hold-in power (W)48 W 68 °F (20 °C)
Heat dissipation22.8...27.8 W
LX9FL926 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate1800 cyc/h 158 °F (70 °C)
Mechanical durability5 Mcycles
LX9FL926 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FL926 is a specific contactor coil from the TeSys F range, designed as a replacement coil for TeSys F contactors. It operates on a 127 V DC control circuit, with low-consumption AC 40...400 Hz and DC control circuit types. This coil has an opening time of 60 ms and a closing time of 20 ms, with a maximum operating rate of 1800 cycles per hour at 158 °F (70 °C). Mechanical durability is rated at 5 Mcycles.

Electrical characteristics and thermal management

The coil draws an inrush power of 733 W at 68 °F (20 °C), with an inrush resistance of 20.8 Ohm. Holding power at 68 °F (20 °C) is 48 W, with a holding resistance of 167 Ohm. Heat dissipation ranges from 22.8 to 27.8 W. Control circuit voltage limits are 0.85...1.1 Uc for operation and 0.3...0.5 Uc for drop-out at 131 °F (55 °C). The coil does not include a built-in suppressor module, so external suppression is needed for inductive load switching. Inductance of the closed circuit is 1.2 H. Ambient air temperature for operation is 23...131 °F (-5...55 °C). The coil technology is without built-in suppressor module.

Frequently asked questions

What is the control voltage for this coil?

The control circuit voltage is 127 V DC, with operational limits of 0.85...1.1 Uc and drop-out limits of 0.3...0.5 Uc at 131 °F (55 °C).

What are the key electrical ratings for the LX9FL926?

Inrush power is 733 W at 68 °F (20 °C), holding power is 48 W at 68 °F (20 °C), and heat dissipation is 22.8...27.8 W. Opening time is 60 ms, closing time is 20 ms.

How do I source the LX9FL926 if it is obsolete?

The LX9FL926 is sourced through the surplus and broker market. Submit an RFQ for current availability and pricing on remaining stock.

MPN