Control circuit and power draw
The LX9FL928: The coil operates on AC 40-400 Hz or DC low consumption (the control circuit type is dual-rated). Inrush power at 20 °C is 733 W; hold-in power at 20 °C is 48 W. Heat dissipation across the operating range is 22.8-27.8 W. The coil has no built-in suppressor module — if you need suppression for the inductive kick, add an external RC snubber or free-wheel diode across the coil terminals.
Lifecycle status is current/active per the manufacturer. No end-of-life notice or successor code is recorded for this coil.
Operating conditions and durability
Mechanical durability is rated at 5 million cycles. Maximum operating rate at 70 °C is 1800 cycles per hour. Ambient air temperature for operation is -5 to 55 °C (23 to 131 °F). Control circuit voltage limits: operational range is 0.85-1.1 Uc at 55 °C; drop-out range is 0.3-0.5 Uc at 55 °C.