Skip to main content
Schneider Electric LX9FL934 — Contactor & Starter Coils

Schneider Electric LX9FL934 TeSys F contactor coil, 300-334

MPNLX9FL934
Active

Schneider Electric TeSys F, specific contactor coil, LX9FL934, 300-334 V DC low consumption.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LX9FL934 — Identification
ParameterValue
Product typeSpecific contactor coil
Product rangeTeSys
Device short nameLX9FL
Coil technologyWithout built-in suppressor module
LX9FL934 — Electrical
ParameterValue
Control circuit voltage [Uc]300...334 V DC
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 131 °F (55 °C))
LX9FL934 — Power & Thermal
ParameterValue
Inrush power (W)733 W 68 °F (20 °C))
Hold-in power (W)48 W 68 °F (20 °C)
Heat dissipation22.8...27.8 W
LX9FL934 — Performance & Durability
ParameterValue
Operating time60 ms opening 20 ms closing
Max. operating rate1800 cyc/h 158 °F (70 °C)
Mechanical durability5 Mcycles
LX9FL934 — Environmental
ParameterValue
Operating temperature23...131 °F (-5...55 °C)

Product details

The LX9FL934 is a specific replacement coil for the TeSys F range of contactors, designed for a control circuit voltage of 300 to 334 V DC. It's a low-consumption coil without a built-in suppressor module, so you'll need to add a free-wheeling diode or RC snubber externally if the circuit requires it. The coil pulls 733 W inrush at 20 °C and holds at 48 W — the inrush is a brief spike, but your DC supply needs to handle that surge without dropping below the 85% operational limit.

The control voltage limits are tight: operational from 0.85 to 1.1 Uc (255 to 367 V DC at 55 °C), drop-out between 0.3 and 0.5 Uc (90 to 167 V DC). If your DC bus sags below 255 V during a brownout, the contactor drops — plan your control transformer or UPS accordingly. Opening time is 60 ms, closing 20 ms — fast enough for most motor and resistive load switching, but if you need arc-sync or zero-cross switching, this coil's mechanical speed is the limiting factor, not the electronics. Rated for 5 million mechanical cycles at a maximum operating rate of 1800 cycles per hour at 70 °C. That's about one operation every two seconds — fine for conveyor cycling or pump start/stop, but not for high-speed pick-and-place or welding gun duty. Heat dissipation runs 22.8 to 27.8 W at full hold — that's non-trivial in a sealed panel. If you're grouping multiple TeSys F contactors, account for this in your thermal budget to avoid derating the coil's ambient temperature range of -5 to 55 °C.

Frequently asked questions

What is the control voltage for the LX9FL934?

It's rated for 300 to 334 V DC control circuit voltage, with an operational range of 0.85 to 1.1 Uc (255 to 367 V DC at 55 °C) and a drop-out range of 0.3 to 0.5 Uc (90 to 167 V DC).

Does the LX9FL934 include a built-in suppressor?

No, it's listed as 'without built-in suppressor module'. You need to add external suppression — typically a free-wheeling diode for DC coils — to protect the control circuit from inductive kickback.

What is the mechanical durability of this coil?

Rated for 5 million mechanical cycles, with a maximum operating rate of 1800 cycles per hour at 70 °C.

MPN