Specifications
| Parameter | Value |
|---|---|
| Product type | Reversing ultra-compact starter |
| Product range / family | TeSys |
| Product name / family | TeSys Hybrid |
| Parameter | Value |
|---|---|
| Rated operational current (Ie), by utilization category | 6.5 A 500 V AC-53A 9 A 500 V AC-51 4.5 A 500 V AC-53A mounting side by side 6 A 500 V AC-51 mounting side by side |
| Rated operational voltage (Ue) | 500 V AC |
| Parameter | Value |
|---|---|
| Number of poles | 3P |
| Auxiliary contact composition | 1 C/O fault signalling |
| Parameter | Value |
|---|---|
| Rated insulation voltage (Ui) | 500 V AC 50/60 Hz |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Parameter | Value |
|---|---|
| Terminal connections / wire range | spring clamp terminals 1 0.0003...0.004 in² (0.2...2.5 mm²) rigid spring clamp terminals 1 0.0004...0.004 in² (0.25...2.5 mm²) flexible - with cable end spring clamp terminals 1 0.0003...0.004 in² (0.2...2.5 mm²) flexible - without cable end |
| IP degree of protection | IP20 |
| Width | 0.9 in (22.5 mm) |
| Height | 3.9 in (99 mm) |
| Depth | 4.5 in (114.5 mm) |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -13...86 °F (-25...30 °C) without derating 86...158 °F (30...70 °C) with derating |
| Storage ambient temperature | -40...176 °F (-40...80 °C) |
| Protective treatment | TC |
| Parameter | Value |
|---|---|
| Certifications | CE CULus |
| Standards | IEC 60947-4-2 UL 60947-4-1 |
| Parameter | Value |
|---|---|
| Thermal protection adjustment range | 1.5...9 A |
MPN