Schneider Electric M9P22740
MPNM9P22740
Active
Miniature circuit breaker (MCB), Multi9 N40N, 3P+N, 40A, C curve, 10kA (IEC/EN 60947-2)
$285.12 – $576.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Miniature circuit-breaker |
| Product name | Multi9 N40 |
| Product range | Multi9 |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Network type (AC/DC) | AC |
| Rated operational voltage [Ue] | 415 V AC 50/60 Hz between phases |
| Rated insulation voltage [Ui] | 500 V AC 50/60 Hz EN/IEC 60947-2 |
| Rated impulse withstand voltage [Uimp] | 4 kVEN/IEC 60947-2 |
| Network frequency | 50/60 Hz |
| Poles description | 3P + N |
| Magnetic tripping limit | 8.5 x In +/- 20 % AC |
| Parameter | Value |
|---|---|
| Breaking capacity | 10 kA Icu 415 V AC 50/60 Hz between phases EN/IEC 60947-2 |
| Rated service breaking capacity [Ics] | 7.5 kA 75 % EN/IEC 60947-2 - 415 V AC 50/60 Hz |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Separate block |
| Suitability for isolation | Yes EN/IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Local signalling | ON/OFF indication |
| Contact position indicator | Yes |
| Parameter | Value |
|---|---|
| Connections / terminals | Tunnel type terminal top or bottom) 0.001...0.02 in² (0.75...16 mm²) - rigid Tunnel type terminal top or bottom) 0.0005...0.02 in² (0.33...10 mm²) - flexible Tunnel type terminal top or bottom) 0.0005...0.02 in² (0.33...10 mm²) - flexible with ferrule |
| Device short name | N40N |
| Control type | Toggle |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Usable 9 mm pitches | 6 |
| Width | 2.1 in (54 mm) |
| Height | 3.2 in (81 mm) |
| Depth | 3.07 in (78 mm) |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 EN/IEC 60947-2 |
| Operating ambient air temperature | -13...158 °F (-25...70 °C) |
| Storage ambient air temperature | -40...158 °F (-40...70 °C) |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| Curve code | C |
| Number of protected poles | 3 |
MPN
M9P22740