Skip to main content
Schneider Electric M9R11263 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric M9R11263

MPNM9R11263
Active

Residual current circuit breaker (RCCB), Multi9 ID, 2P, 63A, AC type, 30mA

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

M9R11263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Local signalling / indicationON, OFF, fault trip
M9R11263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz conforming to EN/IEC 61008-1
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 61008-1
Electrical durability2000 cycles
Mechanical durability (operating cycles)20000 cycles
M9R11263 — Identification
ParameterValue
Product nameMulti9 ID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyMulti9
Device short nameID
M9R11263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal (top or bottom) 1...35 mm² - rigid Tunnel type terminal (top or bottom) 1...25 mm² - flexible Tunnel type terminal (top or bottom) 3 cable(s) 16 mm² - rigid Tunnel type terminal (top or bottom) 3 cable(s) 10 mm² - flexible Tunnel type terminal (top or bottom) 1...25 mm² - flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth73 mm
M9R11263 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...60 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
M9R11263 — Approvals
ParameterValue
StandardsEN/IEC 61008-1
MPN
M9R11263