Skip to main content
Schneider Electric MGN02263 — 2-Pole MCB (DIN Rail)

MGN02263 Acti9 D02 Fuse-Switch Disconnector, 63 A, 2P

MPNMGN02263
Active

Schneider Electric Acti9 D02 fuse-switch disconnector, MGN02263, 2 poles, 63 A, AC-22A/DC-22B, 230-400 V AC, 110 V DC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN02263 — Identification
ParameterValue
Product nameActi9 D0
Series / familyActi9
Device short nameD02
Product / component typeFuse-switch disconnector
MGN02263 — Electrical
ParameterValue
Rated current [In]63 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]230...400 V AC 50/60 Hz 110 V DC
MGN02263 — Protection
ParameterValue
Mechanical durability (cycles)8500 cycles open-close
MGN02263 — Mechanical
ParameterValue
9 mm pitches6
Width72 mm
Height88 mm
Depth68 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsScrew clamp terminals1.5...35 mm² rigid Screw clamp terminals1.5...25 mm² flexible Screw clamp terminals1.5...25 mm² flexible with cable end
Terminal tightening torque3 N.m
MGN02263 — Environmental
ParameterValue
Operating temperature range-5...40 °C
Storage temperature range-25...55 °C
MGN02263 — Approvals
ParameterValue
Standards / complianceIEC 60947-3 EN 60947-1 EN 60947-3 IEC 60269-1 IEC 60947-1 IEC 60269-3

Product details

The MGN02263 is a Schneider Electric Acti9 D02 fuse-switch disconnector — a 2-pole, 63 A unit built for isolating and protecting branch circuits in distribution panels. Rated operational voltage covers 230...400 V AC 50/60 Hz and 110 V DC, with an insulation voltage of 400 V and impulse withstand of 6 kV.

The 63 A rated current and AC-22A utilisation category (per IEC 60947-3) mean this disconnector is rated for switching mixed resistive and inductive loads, including motor circuits with moderate inrush — not just isolating under no-load. The DC-22B rating extends that to DC circuits at 110 V, covering common control-power and battery-backed bus applications. The 6 kV impulse withstand (Uimp) gives it coordination headroom in panels with upstream surge arrestors or high-fault-capacity breakers. Screw-clamp terminals accept 1.5...35 mm² rigid or 1.5...25 mm² flexible conductors, with a tightening torque of 3 N.m and a 14 mm strip length. The 72 mm width (9 mm pitches × 6) fits standard DIN-rail spacing — two of these side-by-side occupy the same footprint as a 4-module MCB.

Frequently asked questions

How do I get current pricing and availability for MGN02263?

Submit an RFQ against this order code — pricing and stock are confirmed at quote time through our independent distribution channel.

What is the closest pin-compatible alternative to MGN02263 in this component family?

There is no official alternative or cross-reference listed for the MGN02263 — it is the current production variant with no direct replacement.

What is MGN02263's listed depth (68 mm) on this component line?

The MGN02263 has a depth of 68 mm, a width of 72 mm, and a height of 88 mm — dimensions that fit standard distribution panel enclosures.

What is MGN02263's listed range (Acti9) on this component line?

The MGN02263 belongs to the Schneider Electric Acti9 range, specifically the D02 series of fuse-switch disconnectors.

What compliance documentation does this brand provide for MGN02263 (RoHS, REACH, UL, IEC)?

The MGN02263 carries VDE quality label and complies with IEC 60947-3, EN 60947-1, EN 60947-3, IEC 60269-1, and IEC 60269-3 standards. RoHS/REACH documentation is typically available from the manufacturer upon request.

MPN
MGN02263