Breaking capacity is 6 kA Icn at 380...415 V AC 50 Hz per EN/IEC 61009-2-1, with a 6 kA Icu rating per EN/IEC 60947-2 at the same voltage. The 30 mA earth-leakage sensitivity covers the standard personnel-protection threshold (IEC 60364), and the device is suitable for isolation (full contact-position indicator on the toggle). Local signalling shows ON, OFF, and fault-trip states — no need to meter the output to confirm a trip.
Clip-on mounting to DIN rail (EN 60715). The module occupies 8 x 9 mm pitches — 72 mm wide — with a depth of 76 mm and height of 85 mm. Tunnel-type terminals accept 1...35 mm² rigid or 1...25 mm² flexible conductors; tighten to 2 N·m. Wire stripping length is 12 mm for top or bottom connection. IP20 on the device face (finger-safe), IP40 inside a modular enclosure per IEC 60529.