Breaking capacity is 6 kA Icn at 380–415 V AC, 50 Hz, per EN/IEC 61009-2-1, with an Icu of 6 kA per EN/IEC 60947-2. The C-curve means the magnetic trip operates between 5 and 10 times the rated current (160–320 A for this 32 A unit), which suits mixed loads with moderate inrush — lighting banks, small motor circuits, or general socket outlets. The 30 mA earth-leakage sensitivity provides personnel protection (30 mA is the standard threshold for shock protection per IEC 60364).
The tunnel-type terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable; strip 12 mm and torque to 2 N·m. Local signalling shows ON, OFF, and fault trip via the toggle. The contact position indicator confirms isolation status — the device is suitability-for-isolation rated (yes). Not padlockable, so if lockout/tagout is required, plan for an external lockable isolator upstream.