It protects a 13 A final circuit against overload, short-circuit, and earth leakage in one unit, saving a DIN rail position compared to a separate MCB + RCCB pair. Breaking capacity is 10 kA Icn / Icu at 220–240 V AC, 50 Hz, certified to EN/IEC 61009-2-1 and EN/IEC 60947-2. The thermal-magnetic trip unit gives you the standard dual-response: thermal for sustained overloads, magnetic for fast short-circuit clearing.
The 76 mm depth and 85 mm height fit standard distribution board envelopes. Tunnel terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable; strip 12 mm and torque to 2 N·m. IP20 finger-safe terminals with IP40 protection inside the modular enclosure. Local signalling shows ON, OFF, and fault trip status — useful for quick fault isolation without a multimeter. The toggle control is the standard actuator; the device is not padlockable, so lockout/tagout requires a separate hasp over the toggle or a downstream isolator.