Schneider Electric MGN19762 — Residual Current Breakers (RCCB/RCBO)

MGN19762 Acti9 DCP Vigi RCBO, 10 A, 30 mA, Curve B, 2P

MPNMGN19762
Obsolete

Schneider Electric Acti9 DCP Vigi RCBO, MGN19762, 2P, 10 A rated, 30 mA earth leakage, curve B, 10 kA breaking capacity, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

MGN19762 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
MGN19762 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
MGN19762 — Identification
ParameterValue
Product nameActi9 DCP Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameDCP H Vigi
MGN19762 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth76 mm
MGN19762 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
MGN19762 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The MGN19762 is a 2-pole RCBO (residual current breaker with overcurrent protection) from the Acti9 DCP Vigi range, rated 10 A with a 30 mA earth-leakage sensitivity and a B tripping curve (3–5 × In magnetic release). That 30 mA sensitivity is the standard for personal protection against indirect contact in final circuits — it covers the same ground as a standalone RCCB but integrated into one module. The thermal-magnetic trip technology is the conventional dual-element type — bimetal strip for overload, solenoid for short-circuit. Clip-on mounting onto a DIN rail (35 mm per EN 60715) at 4 module pitches (36 mm per pole width) means it occupies 72 mm of rail space.

The 8/20 µs impulse withstand of 250 A confirms electromagnetic compatibility per that same standard. Tropicalisation class 2 indicates the part is treated for humidity and mould resistance in warm climates. The contact-position indicator (ON/OFF/fault trip) and suitability for isolation (EN 60947-2) mean it can serve as a local disconnection point when locked off — though it is not padlockable, so a separate lockout device would be needed for LOTO procedures.

Frequently asked questions

How do I get current pricing and availability for MGN19762?

Pricing and availability are confirmed at quote time against an RFQ through independent distribution channels.

What is the closest alternative to MGN19762 in the Acti9 range?

Within the Acti9 DCP Vigi family, the closest sibling would differ only in rated current or curve code — for example a 16 A or C-curve variant. The 2P, 30 mA, 10 kA platform is shared; the selection depends on the load's inrush characteristic and the circuit's ampacity.

What is MGN19762's listed depth (76 mm) on this component line?

The MGN19762 has a depth of 76 mm, with a width of 36 mm (2 module pitches) and height of 85 mm.

What compliance documentation does this brand provide for MGN19762?

The part is certified to EN/IEC 61009-2-1 and EN/IEC 60947-2. The manufacturer typically provides a declaration of conformity covering the applicable EU directives; specific RoHS/REACH declarations are available on request from the supplier.

MPN
MGN19762