Skip to main content
Schneider Electric MGN25080 — 1-Pole MCB (DIN Rail)

MGN25080 C60H MCB, 1 A, Curve D, 1P, 15 kA, Multi9

MPNMGN25080
Obsolete

Schneider Electric C60H Multi9 miniature circuit breaker, MGN25080, 1 A rated, curve D, 1 pole, 15 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25080 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN25080 — Electrical & Protection
ParameterValue
Rated current (In)1 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN25080 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN25080 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN25080 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN25080 is a 1 A, 1-pole C60H miniature circuit breaker from the Multi9 range, curve D, rated at 240 V AC phase-to-neutral. The 1 A rating at 50 °C per EN/IEC 60947-2 sets the continuous current the breaker carries without derating — if your ambient runs hotter, you need to account for that. The Ics (service breaking capacity) is 7.5 kA at 240 V AC, 50% of Icu, meaning after one fault at that level the breaker is still usable but should be inspected.

Deployment context

Snaps onto a 35 mm symmetrical DIN rail (EN 60715) and occupies 2 x 9 mm pitches (18 mm wide). The tunnel terminals accept 1 to 25 mm² rigid or flexible wire; strip length is 14 mm and tighten to 2 N·m. The toggle provides local ON/OFF indication and a contact position indicator confirms isolation status.

Frequently asked questions

Where can I buy MGN25080?

The MGN25080 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest alternative to MGN25080?

Within the C60 family, the C60N (lower breaking capacity, typically 10 kA at 240 V) is a common alternative if the fault current allows. The C60H (this part) is the higher-breaking-capacity variant. No pin-compatible drop-in exists with a different curve or pole count.

MPN
MGN25080