Skip to main content
Schneider Electric MGN25084 — 1-Pole MCB (DIN Rail)

MGN25084 C60H MCB, 1P D-curve 6 A, 15 kA at 240 V

MPNMGN25084
Obsolete

Schneider Electric Multi9 C60H series, MGN25084 miniature circuit-breaker, 1-pole, D-curve, 6 A rated, 15 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25084 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN25084 — Electrical & Protection
ParameterValue
Rated current (In)6 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN25084 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN25084 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN25084 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN25084 is a C60H miniature circuit-breaker from the Multi9 range — a 1-pole, D-curve unit rated 6 A at 50 °C per EN/IEC 60947-2. The D-curve magnetic trip triggers at 12 x In ±20 %, so it tolerates the inrush of motor loads, transformers, or welding equipment without nuisance tripping.

Snaps onto 35 mm symmetrical DIN rail — standard panel layout, 18 mm per pole width, 2 module pitches. The 73 mm depth fits shallow enclosures; leave clearance for the toggle handle and wiring. Rated for isolation (EN/IEC 60947-2) with a visible contact-position indicator, so you can lock it out as a disconnecting means. Pollution degree 3 means it handles conductive dust and condensation typical of industrial control rooms. Ambient operating range -30 to 70 °C covers most plant-floor conditions without derating.

Selectivity and coordination

Frequently asked questions

What is MGN25084's breaking capacity?

The MGN25084 has a breaking capacity of 15 kA Icu at 240 V AC phase-to-neutral per EN/IEC 60947-2, and 4 kA Icu at 415 V AC phase-to-neutral.

What does the D-curve mean on this breaker?

The D-curve magnetic trip activates at 12 x In ±20 %, designed to handle high inrush currents from motor loads, transformers, or welding equipment without nuisance tripping.

Where can I buy MGN25084?

The MGN25084 is available to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What compliance standards does MGN25084 meet?

The MGN25084 is certified to EN/IEC 60947-2, rated for isolation, and carries pollution degree 3 classification. It is suitable for use in distribution boards requiring IEC 60947-2 compliance.