Schneider Electric MGN25085 — 1-Pole MCB (DIN Rail)

MGN25085 C60H MCB, D Curve 10 A, 1P, 15 kA

MPNMGN25085
Obsolete

Schneider Electric Multi9 C60H series, MGN25085, miniature circuit breaker, 1P, D curve, 10 A rated, 15 kA Icu at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25085 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN25085 — Electrical & Protection
ParameterValue
Rated current (In)10 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN25085 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN25085 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN25085 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN25085 is a 1-pole C60H miniature circuit breaker from the Multi9 range, rated 10 A at 50 °C per EN/IEC 60947-2. The 15 kA Icu at 240 V AC phase-to-neutral is the maximum fault current it can safely interrupt; the Ics (service breaking capacity) is 7.5 kA at the same voltage, which is 50 % of Icu and tells you it can be reclosed after a fault at that level without immediate replacement. At 415 V AC the Icu drops to 4 kA and Ics to 2 kA — if your panel feeds a 400 V line-to-line circuit, this breaker is not the right choice; you need a higher-rated C60H variant or a different frame.

The single-pole module occupies 18 mm (2 x 9 mm pitches) — standard width, no surprises in a populated enclosure. IP20 rated, so it is for dry indoor panels only, not washdown areas.

Frequently asked questions

What is MGN25085's D curve magnetic trip threshold?

The D curve trips magnetically at 12 x In ±20 %, meaning the 10 A breaker will instantaneously trip between roughly 96 A and 144 A — designed for high-inrush loads like small motors and transformers.

What is the breaking capacity of MGN25085 at 240 V and 415 V?

At 240 V AC the Icu is 15 kA and Ics is 7.5 kA; at 415 V AC the Icu is 4 kA and Ics is 2 kA.

Where can I buy MGN25085 and how is it quoted?

The MGN25085 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
MGN25085