Skip to main content
Schneider Electric MGN25088 — 1-Pole MCB (DIN Rail)

MGN25088 C60H MCB, 25 A, Curve D, 1P, 15 kA

MPNMGN25088
Obsolete

Schneider Electric C60H Multi9 miniature circuit-breaker, 1P, 25 A rated, curve D, 15 kA breaking capacity at 240 V AC, thermal-magnetic trip, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25088 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN25088 — Electrical & Protection
ParameterValue
Rated current (In)25 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN25088 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN25088 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN25088 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN25088 is a C60H miniature circuit-breaker from the Multi9 range, rated 25 A at 50 °C per EN/IEC 60947-2.

Deployment context

Snaps onto 35 mm symmetrical DIN rail inside a distribution panel or sub-board. The toggle gives local ON/OFF indication — useful for a panel wireman tracing circuits during commissioning.

Frequently asked questions

What is the breaking capacity of MGN25088?

15 kA Icu at 240 V AC 50/60 Hz phase-to-neutral, and 4 kA Icu at 415 V AC, both per EN/IEC 60947-2. The service breaking capacity (Ics) is 50 % of those values.

MPN
MGN25088