Schneider Electric MGN25089 — 1-Pole MCB (DIN Rail)

MGN25089 C60H MCB, D Curve, 32 A, 1P, 15 kA

MPNMGN25089
Obsolete

Schneider Electric C60H Multi9 series, MGN25089, miniature circuit breaker, 1P, D curve, 32 A rated current, 15 kA Icu at 240 V AC, 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25089 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN25089 — Electrical & Protection
ParameterValue
Rated current (In)32 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)15 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 4 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN25089 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 3.5 N.m
MGN25089 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN25089 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN25089 is a Schneider Electric C60H miniature circuit breaker from the Multi9 range, rated 32 A at 50 °C with a D trip curve. It protects a single pole (1P) in AC distribution networks at 240 V phase-to-neutral. The thermal-magnetic trip unit handles overloads via the bimetal strip and short-circuits via the solenoid. Breaking capacity is 15 kA Icu at 240 V AC and 4 kA Icu at 415 V AC, both per EN/IEC 60947-2. The service breaking capacity (Ics) is 50 % of Icu: 7.5 kA at 240 V, 2 kA at 415 V. That means after clearing a fault at these levels the breaker remains functional, not just safe.

Depth is 73 mm, height 81 mm. Tunnel terminals accept 1.5 to 35 mm² rigid or flexible wire; tightening torque is 3.5 N·m. Strip length 14 mm. IP20 finger protection on the front.

Suitable for isolation (marked with the open-contact indicator). The toggle provides local ON/OFF indication. Earth-leakage protection requires a separate block — this is the MCB only. Electrical endurance is 10,000 cycles, mechanical 20,000 cycles. Utilisation category A (non-delayed short-circuit release).

Frequently asked questions

What is the breaking capacity of MGN25089?

15 kA Icu at 240 V AC and 4 kA Icu at 415 V AC, both per EN/IEC 60947-2. The service breaking capacity (Ics) is 50 % of those values: 7.5 kA at 240 V and 2 kA at 415 V.

What compliance standards does MGN25089 meet?

It is certified to EN/IEC 60947-2, pollution degree 3, suitable for isolation. IP20 front protection. The thermal-magnetic trip unit is standard for this class. Earth-leakage protection requires an add-on block.

MPN
MGN25089