Skip to main content
Schneider Electric MGN25111 — 2-Pole MCB (DIN Rail)

MGN25111 C60H MCB, 2A D-curve 2P 30kA, Multi9

MPNMGN25111
Obsolete

Schneider Electric Multi9 C60H series, MGN25111 miniature circuit breaker, 2 A rated current, D-curve, 2-pole, 30 kA breaking capacity at 240 V AC, 73 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25111 — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN25111 — Electrical
ParameterValue
Rated current [In]2 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
MGN25111 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN25111 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Comb busbar / distribution block compatibilityTop or bottom: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN25111 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
MGN25111 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

The MGN25111 is a Schneider Electric C60H miniature circuit breaker from the Multi9 range, rated 2 A with a D-curve trip characteristic and 2-pole configuration.

Rated service breaking capacity (Ics) is 15 kA at 240 V AC (50 % of Icu), 7.5 kA at 415 V, and 5 kA at 440 V. That Ics figure governs the fault-clearing capability after one trip — the breaker remains functional, not just safe. For distribution panels where a downstream fault must be cleared without upstream interruption, the D-curve and 30 kA Icu at 240 V give headroom for selective coordination with a larger upstream device.

The 73 mm depth fits standard distribution enclosures with cover clearance.

Frequently asked questions

Where can I buy MGN25111 and how do I get a price?

The MGN25111 is sourced to order through independent distribution. Submit an RFQ for current pricing and availability.

What is MGN25111's rated breaking capacity?

The MGN25111 has a 30 kA Icu at 240 V AC phase-to-phase conforming to EN/IEC 60947-2, with an Ics of 15 kA at that voltage.

What compliance standards does MGN25111 meet?

The MGN25111 is certified to EN/IEC 60947-2, with pollution degree 3, and is suitable for isolation per that standard.

MPN
MGN25111