Skip to main content
Schneider Electric MGN25115 — 2-Pole MCB (DIN Rail)

MGN25115 C60H MCB, 2P D-Curve 10 A, 30 kA Breaking Capacity

MPNMGN25115
Obsolete

Schneider Electric Multi9 C60H series, MGN25115 miniature circuit breaker, 2-pole D-curve, 10 A rated current, 30 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN25115 — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
MGN25115 — Electrical
ParameterValue
Rated current [In]10 A at 50 °C conforming to EN/IEC 60947-2
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Network type (AC/DC)AC
Network frequency50/60 Hz
MGN25115 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]15 kA 50 % conforming to EN/IEC 60947-2 - 240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Suitable for isolationYes conforming to EN/IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
MGN25115 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Terminal connectionsTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Terminal tightening torquePower circuit: 2 N.m
Comb busbar / distribution block compatibilityTop or bottom: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
MGN25115 — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...80 °C
MGN25115 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2

Product details

The MGN25115 is a 2-pole D-curve miniature circuit breaker from the Schneider Electric Multi9 C60H range, rated 10 A at 50 °C per EN/IEC 60947-2. The D-curve magnetic trip at 12 x In (±20 %) means it tolerates the inrush of motor starters and small transformers without nuisance tripping, which is exactly what you need when this breaker feeds a contactor coil or a control transformer on the same panel.

At 36 mm wide (4 x 9 mm pitches) it occupies two module spaces, so factor that into your rail fill. The toggle provides local ON/OFF indication with a contact position indicator that confirms the state even if the handle is forced — a detail that matters during panel commissioning when you need to verify isolation at a glance.

Rated operational voltage is 440 V AC, with the service breaking capacity (Ics) at 50 % of Icu across the voltage range — 15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V. Earth-leakage protection requires a separate block — this is the thermal-magnetic MCB only, not an RCBO.

Frequently asked questions

Where can I buy MGN25115 and how do I get a price?

The MGN25115 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the closest alternative to MGN25115 in the C60 family?

Within the same C60 platform, the difference between the C60H (this part) and the standard C60 or C60N is the breaking capacity. The C60H carries 30 kA Icu at 240 V AC versus 10 kA or 20 kA on the lower tiers. If your fault level is below 10 kA, a standard C60 D-curve 2P 10 A may fit the same DIN footprint and terminal range, but verify the SCCR at your point of installation before substituting.

What is MGN25115's listed depth?

The MGN25115 has a depth of 73 mm, with a width of 36 mm and a height of 81 mm. The 36 mm width corresponds to 4 x 9 mm DIN-rail pitches (two module spaces).

What compliance documentation does this brand provide for MGN25115?

The MGN25115 is certified to EN/IEC 60947-2, with IP20 degree of protection per that standard. It carries suitability for isolation marking and a pollution degree 3 rating. For specific RoHS, REACH, or UL documentation, request the manufacturer's compliance declaration with your RFQ.

MPN