Skip to main content
Schneider Electric MGN25118

MGN25118 C60H MCB, 20 A D-curve 2P, 30 kA breaking

MPN MGN25118
Obsolete

Schneider Electric C60H Multi9 miniature circuit breaker, MGN25118, 20 A rated, D-curve, 2-pole, 30 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN25118 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN25118 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

What the D-curve and 20 A rating mean for your panel

The MGN25118 is a C60H miniature circuit breaker from the Multi9 range, rated 20 A at 50 °C with a D-curve magnetic trip of 12 x In +/- 20 %.

Breaking capacity and service continuity — the real coordination numbers

But the service breaking capacity Ics tells you what it can do repeatedly: 15 kA at 240 V (50 % of Icu), 7.5 kA at 415 V, and 5 kA at 440 V. For a distribution board downstream of a transformer with a 10 kA prospective fault current, this breaker gives you full selectivity with the upstream device. The Category A utilisation rating means it's not intended for cascading with a downstream breaker — it's the load-end device in a coordinated scheme.

Mounting and wiring — DIN-rail fit and terminal details

Standards and compliance — what the approvals cover

Isolation suitability is confirmed — the contact position indicator gives positive visual confirmation of open contacts, meeting the safety isolation requirements of IEC 60947-2. The separate earth-leakage block option (sold separately) lets you add RCD protection without swapping the breaker.

MPN