Skip to main content
Schneider Electric MGN25119

Schneider Electric MGN25119 C60H MCB, 25 A, 2P, D Curve, 30

MPN MGN25119
Obsolete

Schneider Electric C60H Multi9 miniature circuit breaker, MGN25119, 2-pole, 25 A, D curve, 30 kA breaking capacity at 240 V AC, thermal-magnetic trip, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN25119 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage440 V AC 50/60 Hz 240 V AC 50/60 Hz phase to phase
Breaking capacity30 kA Icu at 240 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz phase to phase conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN25119 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The Schneider Electric MGN25119 is a C60H miniature circuit breaker from the Multi9 range, rated 25 A at 50 °C per EN/IEC 60947-2, with a D trip curve and 2 protected poles. It is a thermal-magnetic device, category A, designed for distribution applications where high inrush currents (motor starts, transformer primaries, lighting ballasts) demand the D curve's wider magnetic trip threshold of 12 x In ±20 %.

The C60H frame delivers 30 kA Icu at 240 V AC phase-to-phase, 15 kA at 415 V, and 10 kA at 440 V — all per EN/IEC 60947-2. The corresponding Ics (service breaking capacity) is 50 % of Icu at each voltage level: 15 kA at 240 V, 7.5 kA at 415 V, 5 kA at 440 V.

IP20 finger-safe front.

MPN
MGN25119