Skip to main content
Schneider Electric MGN60510 — 1-Pole MCB (DIN Rail)

MGN60510 C60N MCB, D Curve 6 A, 10 kA Breaking Capacity

MPNMGN60510
Obsolete

Schneider Electric C60N Multi9 miniature circuit breaker, MGN60510, 1P, D curve, 6 A rated, 10 kA breaking capacity at 240 V AC, 35 mm DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60510 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60510 — Electrical & Protection
ParameterValue
Rated current (In)6 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60510 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN60510 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60510 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN60510 is a C60N miniature circuit breaker from the Multi9 range, rated 6 A at 50 °C with a D tripping curve. The 10 kA Icu at 240 V AC (phase-to-neutral) is the maximum fault current it can safely interrupt; the Ics service breaking capacity is 7.5 kA (75 % of Icu) at the same voltage, which tells you it can reclose after a fault at that level.

The 73 mm depth leaves clearance for standard enclosure depths. The toggle gives local ON/OFF indication and the contact position indicator confirms isolation status, which is useful during panel commissioning.

Frequently asked questions

What is the breaking capacity of MGN60510?

The MGN60510 is rated 10 kA Icu at 240 V AC 50/60 Hz phase-to-neutral, with an Ics of 7.5 kA (75 %) at the same voltage, per EN/IEC 60947-2.

What does the D curve mean on this MCB?

The D curve sets the magnetic trip threshold at 12 x In (±20 %), designed for loads with high inrush current such as motors, transformers, and welding equipment.

Where can I buy MGN60510 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

What compliance documentation is available for MGN60510?

The MCB is certified to EN/IEC 60947-2, with pollution degree 3, and the declared short-circuit ratings (10 kA Icu, 7.5 kA Ics) are documented for panel certification.

MPN
MGN60510