Skip to main content
Schneider Electric MGN60511 — 1-Pole MCB (DIN Rail)

MGN60511 C60N MCB, 1P D10, 10 kA, Multi9

MPNMGN60511
Obsolete

Schneider Electric Multi9 C60N series, MGN60511 miniature circuit breaker, 1-pole, D-curve, 10 A rated, 10 kA breaking capacity per EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60511 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60511 — Electrical & Protection
ParameterValue
Rated current (In)10 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60511 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN60511 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60511 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN60511 is a C60N miniature circuit breaker from Schneider Electric's Multi9 range, built for distribution-level overcurrent protection. It's a single-pole unit with a D-curve trip characteristic, rated 10 A at 50 °C per EN/IEC 60947-2, and carries a 10 kA Icu breaking capacity at 240 V AC phase-to-neutral.

D-curve and selectivity

A standard B-curve would nuisance-trip on the start-up surge; the D-curve holds through the inrush and clears only on a hard fault. For a 10 A unit, that means magnetic trip between roughly 96 A and 144 A. That matters for uptime in distribution boards where a downstream short shouldn't scrap the protective device.

Frequently asked questions

What is the breaking capacity of MGN60511?

The MGN60511 has a 10 kA Icu breaking capacity at 240 V AC phase-to-neutral per EN/IEC 60947-2, with an Ics of 7.5 kA at the same voltage.

What does the D-curve on MGN60511 mean?

The D-curve trips magnetically at 12 x In ±20%, so for this 10 A breaker the magnetic trip range is 96 A to 144 A, designed to handle high inrush loads like motors and transformers without nuisance tripping.

Where can I buy MGN60511 and get current pricing?

MGN60511 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
MGN60511