Skip to main content
Schneider Electric MGN60514 — 1-Pole MCB (DIN Rail)

MGN60514 C60N MCB, 1P D 25 A, 10 kA, Multi9

MPNMGN60514
Obsolete

Schneider Electric Multi9 C60N series, MGN60514 miniature circuit breaker, 1-pole, D-curve, 25 A rated current, 10 kA breaking capacity at 240 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60514 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60514 — Electrical & Protection
ParameterValue
Rated current (In)25 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60514 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1.5...35 mm² flexible without cable end Tunnel type terminals1.5...35 mm² flexible with cable end Tunnel type terminals1.5...35 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN60514 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60514 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN60514 is a 1-pole C60N miniature circuit breaker from the Multi9 range, rated 25 A at 50 °C per EN/IEC 60947-2 with a D-curve magnetic trip threshold of 12 x In ±20 %. The 10 kA Icu at 240 V AC phase-to-neutral covers most residential and light commercial distribution panels; the service breaking capacity (Ics) is 7.5 kA at the same voltage, which is 75 % of Icu — adequate for routine fault clearing without immediate replacement. The thermal-magnetic trip unit combines a bimetal element for overload protection and a solenoid for short-circuit response, both factory-calibrated and sealed.

Snaps onto a 35 mm symmetrical DIN rail (EN 60715) and occupies 2 x 9 mm pitches (18 mm total width). The fixed mounting mode and tunnel-type terminals accept 1.5 to 35 mm² rigid or flexible conductors; strip length is 14 mm and tightening torque is 2 N·m for the power circuit. IP20 finger-safe terminals are standard for enclosed panel use.

Frequently asked questions

What is the breaking capacity of MGN60514?

The MGN60514 has a rated breaking capacity (Icu) of 10 kA at 240 V AC phase-to-neutral per EN/IEC 60947-2, and 3 kA at 415 V AC. The service breaking capacity (Ics) is 7.5 kA at 240 V AC (75 % of Icu).

What is the rated current and curve of MGN60514?

The MGN60514 is rated 25 A at 50 °C with a D-curve trip characteristic — magnetic tripping occurs at 12 x In ±20 %, designed for loads with high inrush current such as motors and transformers.

Where can I buy MGN60514 and how is it quoted?

The MGN60514 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

MPN
MGN60514